| Date |
Text |
| 2009-06-26 17:57:58 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. IT APPEARS THAT THIS PARCEL MAY BE LOCATED IN A HIGH |
| | HAZARD FLOOD ZONE. THE STRUCTURE IS TO COMPLY WITH WPB |
| | ADMIN CODE 94-546(B). PLEASE NOTE FINISHED FLOOR |
| | ELEVATION, MINIMUM 6" ABOVE BASE FLOOD, ON THE PLAN AND |
| | PROVIDE THE FLOOD ELEVATION CERTIFICATE. A FORM BOARD |
| | ELEVATION CERTIFICATE AS WELL AS A FINAL ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. |
| | |
| | 2. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR |
| | TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 3. RADON FEES DUE, FS*553.721. SEE ATTACHED. |
| | |
| | 4. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2). SOME SHEETS REFER TO ATTACHED FIRE |
| | SPRINKLER/FIRE ALARM PLANS, BUT THEY WERE NOT INCLUDED. |
| | |
| | 5. PLEASE SEE ZONING COMMENTS AND CLARIFY LOCATION OF |
| | PARCEL LINES. PLEASE CLARIFY LOCATION OF IMPROVEMENTS |
| | IN RELATION TO THE LEGAL RECORDED LOT LINES/PLAT. THE |
| | TRACTS SHOWN ON THE PLAN ARE NOT CONSISTENT WITH COUNTY |
| | RECORDS. WWW.PBCGOV.COM/PAPA, WWW.PBCOUNTYCLERK.COM |
| | |
| | 6. AREA INCREASE CALCULATIONS ARE TO BE INCLUDED ON THE |
| | PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503, SHEET A1. |
| | |
| | 7. STORAGE AREAS AND A CONFERENCE ROOM (ASSEMBLY) ARE |
| | SHOWN. PLEASE INCLUDE THESE AREAS IN THE AREA |
| | CALCULATIONS, SHEET A1, FBC508.1. ANY ACCESSORY OR |
| | INCIDENTAL USE AREAS ARE TO BE NOTED AS SUCH WITH |
| | APPROPRIATE FIRE RESISTIVE SEPARATIONS NOTED ON THE |
| | PLAN (BOTH HORIZONTAL AND VERTICAL), FBC TABLE 508.2, |
| | FBC 508.3.1. |
| | |
| | 8. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1. FIRE |
| | RATING FOR FIRE BARRIER NOT SHOWN, A1, WALL SYMBOLS. |
| | SPECIFY FIRE RESISTIVE RATING AND PROVIDE A DETAIL, |
| | FBC703.2. |
| | |
| | 9. STAIR CONSTRUCTION TO COMPLY WITH FBC1020.1.4, |
| | PLEASE NOTE REQUIRED FIRE RESISTANCE ON WALLS WITHIN |
| | 10FT AS WELL AS OPENINGS WITHIN THE 10FT. PROVIDE |
| | PRODUCT APPROVAL FOR THE FIRE RATED WINDOW AND IMPACT |
| | PROTECTION, FAC9B72. |
| | |
| | 10. A1, PLEASE REVISE OCCUPANT LOAD, TAKING INTO |
| | ACCOUNT CONFERENCE ROOM AREA, SEE FBC TABLE 1004.1.1. |
| | |
| | 11. THE FILE STORAGE/IT AREA IS NOTED AS A FIRE PROOF |
| | AREA, BUT FIRE RESISTANCE IS NOT SPECIFIED ON THE PLAN, |
| | SEE A1, WALL SYMBOLS. SEE OTHER COMMENTS REGARDING |
| | OCCUPANCY CLASSIFICATION AND REQUIRED SEPARATIONS. SHOW |
| | ALL REQUIRED FIRE RATINGS ON THE PLAN, BOTH HORIZONTAL |
| | AND VERTICAL, FBC 7. |
| | |
| | 12. SHOW MANEUVERING CLEARANCE, PULL SIDE, ON THE |
| | FOLLOWING DOORS PER FBC FIGURE 11-25: |
| | |
| | EXEC. OFFICE 10, SOUTHEAST CORNER |
| | CEO OFFICE 5, NORTH DOOR |
| | |
| | 13. TR 5, CEO OFFICE 5, IS TO BE ADAPTABLE, |
| | FBC11-4.1.3(11). SHOW BLOCKING FOR FUTURE GRAB BARS, |
| | TURNING RADIUS. |
| | |
| | 14. JANITOR'S CLOSET SHALL BE CONSTRUCTED SO THAT |
| | EMPLOYEES WITH DISABILITIES CAN APPROACH, ENTER, AND |
| | EXIT THE AREA FBC11-4.1(3). |
| | |
| | 15. STAIRS, SHOW PROTECTION FROM OVERHEAD HAZARDS, FBC |
| | FIGURE 11-8 (C1). |
| | |
| | 16. PROVIDE A DETAIL FOR THE ACCESSIBLE PARKING SPACE, |
| | INCLUDING ACCESS AISLE. PLEASE INCLUDE SLOPE AND CROSS |
| | SLOPE. FBC FIGURE 11-10. |
| | |
| | 17. TR2, 2ND FLOOR, CLEAR FLOOR SPACE FOR THE LAV |
| | CANNOT ENCROACH INTO THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE WATER CLOSET. FBC FIGURE 11-30E. |
| | |
| | 18. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | FOR THE ROOF HATCH, FAC9B72. SEE ALSO DCA DECLARATORY |
| | STATEMENT CONFIRMING THIS REQUIREMENT. THIS MAY BE A |
| | PROVISO ITEM UPON REQUEST BUT MUST BE PROVIDED PRIOR TO |
| | INSTALLATION. |
| | |
| | 19. A3 SHOWS A BACKUP GENERATOR ON THE ROOF, S103 DOES |
| | NOT APPEAR TO INCLUDE THE GENERATOR. PLEASE ADDRES, |
| | FBC16. |
| | |
| | 20. FBC13-103.1.1.1, DESIGN PROFESSIONALS RESPONSIBLE |
| | UNDER FLORIDA LAW FOR THE DESIGN OF THE BUILDING SHELL, |
| | SHALL CERTIFY COMPLIANCE OF THOSE BUILDING SYSTEMS WITH |
| | THE CODE BY SIGNING AND PROVIDING THEIR PROFESSIONAL |
| | REGISTRATION NUMBER ON THE ENERGY CODE FORM PROVIDED AS |
| | PART OF THE PLANS AND SPECIFICATIONS TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 21. FOR THE MODIFIED ROOF SYSTEM, PLEASE INDICATE WHICH |
| | APPROVED ASSEMBLY WILL BE INSTALLED, FASTENER SELECTED, |
| | AND ENHANCED FASTENING SPECIFICATION IN ACCORDANCE WITH |
| | RAS117 (PREPARED BY AN ARCHITECT, ENGINEER, OR |
| | REGISTERED ROOF CONSULTANT); SEE GENERAL LIMITATION #7 |
| | ON THE NOA. THIS CAN BE A PROVISO ITEM, TO BE PROVIDED |
| | AT TIME OF ROOF PERMIT SUBMITTAL. |
| | |
| | 22. FOR THE ROOF TILE, PLEASE INDICATE METHOD OF |
| | ATTACHMENT. IF FOAM ADHESIVE IS PROPOSED, PLEASE |
| | PROVIDE PRODUCT APPROVAL FAC9B72. THIS CAN BE A PROVISO |
| | ITEM, TO BE PROVIDED AT TIME OF ROOF PERMIT SUBMITTAL. |
| | |
| | 23. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. PLEASE SUBMIT TWO ORIGINAL SOILS REPORTS. |
| | |
| | 24. ENERGY CALC SHOWS A BUILT UP ROOF, R19. PLEASE |
| | PROVIDE CLARIFICATION. A3 SHOWS 2" INSULATION BOARD; |
| | PROVIDE SPEC SHEETS FOR THE INSULATION TO SHOW THAT IT |
| | MEETS THE MINIMUM R19 REQUIREMENT. |
| | |