| 2009-06-29 16:33:55 | |
| | ** DENIED REVIEW ** |
| | |
| | ** PLANS SUBMITTED ARE NOT COMPLETE FOR *MINIMUM CODE |
| | COMPLIANCE*. PLEASE KNOW THERE MAY BE NEW COMMENTS ON |
| | THE FOLLOWING REVIEW ONCE INFORMATION IS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS SHOWING MINIMUM DESIGNS |
| | AND INSTALLATIONS PER CODES WHICH ARE REQUIRED TO BE |
| | REFLECTED ON PLANS. |
| | THE INCORRECT CODES ARE STATED. |
| | PLANS SHOULD REFLECT THE FOLLOWING CODES AT A MINIMUM |
| | FOR ELECTRICAL REVIEW. |
| | |
| | 2007 FBC WITH 2009 REVISIONS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2002 NFPA-72 ( WHERE APPLICABLE) |
| | |
| | 2) NOTE: PLEASE SUBMIT AND SHOW COMPLIANCE FOR NEW |
| | LIGHTING CONTROLS BEING INSTALLED FOR MINIMUM |
| | PRESCRIPTIVE COMPLIANCE UNDER FBC 13-415.AB.1.1,.1.2, |
| | .1.3. |
| | |
| | 3) NOTE: PLEASE SHOW COMPLIANCE WITH FBC 13-415.AB.5 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE KNOW THAT |
| | NEW LIGHTING MAY NOT BE ADDED UNLESS THE EXISTING |
| | LEVELS WITH NEW CAN BE CONFIRMED. |
| | |
| | 4) NOTE: RISER IS MISSING METHOD OF EQUIPMENT GROUNDING |
| | AFTER THE FIRST MEANS OF DISCONNECT. PLEASE ALSO |
| | INCLUDE NOTE FOR FLOATING NEUTRAL KIT REQUIRED. |
| | 250.6,250.24,250.110, 250.122 ETC |
| | |
| | 5) NOTE: PLEASE SEE RISER. THE RISER SHOWS THE 200AMP |
| | PANEL BEING FED FROM THE 400 AMP MLO, HOWEVER THE PANEL |
| | SCHEDULE DOES NOT INCLUDE ANY SUB FEED FOR THE 200AMP |
| | PANEL. NO INFORMATION ON A BRANCH BREAKER OR ANY OTHER |
| | MEANS TO FEED THE NEW SUB PANEL. |
| | 240.4,310.16, 215.5 ETC. |
| | FBC 106.1.1,106.1.2,106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE COORDINATE LOCATION OF PROJECT ON ALL |
| | SHEETS/PLANS AND DOCUMENTS SUBMITTED. SOME SHOW 6901 |
| | OKEECHOBEE BLVD, SOME SHOW 1910 OKEECHOBEE BLVD, |
| | FAC 61G1-16.004, 61G15-23.002, FBC 106.5 |
| | |
| | 7) NOTE: COVENANT CONSULTING GROUP SHALL INDICATE THEIR |
| | REQUIRED LICENSING ON PLANS/TITLE BLOCKS PER |
| | FAC61G15-23.002, FS 471.023. |
| | DESIGN FIRMS NOT LICENSED UNDER FS 471, 481 SHALL NOT |
| | DESIGN OR BE PART OF COMMERCIAL BUILDINGS AND DESIGN |
| | PROJECTS. FS 481.229, 471.003 |
| | |
| | 8) NOTE: AS OF THE DATE OF THIS REVIEW, THE LICENSE FOR |
| | FIRM LISTED ON TITLE BLOCKS AS GMB ENGINEERING INC IS |
| | CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF BUSINESS |
| | AND PROFESSIONAL REGULATION. A PRINT OUT HAS BEEN |
| | ATTACHED TO REVIEW NOTES WHICH INDICATES THE STATUS AS |
| | OF 6/29/09, 4:06 PM. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |