| Notes |
| Date |
Text |
| 2009-10-10 08:14:49 | ** DENIED** | | | | | | 1) NOTE: NEW LIGHTING AND EXISTING LIGHTING APPEAR TO | | | MEET REQUIRED MINIMUMS HOWEVER NEW LIGHTING DOES NOT | | | INDICATE HOW OR WHERE THESE WILL BE CONTROLLED? | | | FBC 13-415.AB.1.1,.1.2 | | | NO CIRCUITING ON PLANS TO SHOW WHERE LIGHTS WOULD BE | | | FED. SEE 700.12F FOR UNIT EMERGENCY LIGHT FIXTURES TO | | | LOCAL LIGHTING BRANCH CIRCUIT. | | | | | | ** THE ABOVE COULD HAVE BEEN A PROVISO HOWEVER AS THERE | | | ARE STILL BUILDING REVIEW COMMENTS THIS SHEET COULD NOT | | | BE STAMPED OR GIVEN A PROVISO AT THIS TIME. | | | | | | **IMPORTANT** | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|