| 2009-10-01 15:48:04 | BUILDING PLAN REVIEW |
| | PERMIT: 09060076 |
| | ADD: 1335 OKEECHOBEE RD SUITE# 1000 |
| | CONT: ATLANTIC GENERAL CONTRACTING |
| | TEL: (561)434-4171 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | NO CHANGE IN INFORMATION! |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. PLEASE UPDATE PLANS TO |
| | ALSO INCLUDE THE 2007 EXISTING BUILDING CODE, CHAPTER |
| | 10 ADDITIONS (MEZZANINE ADDING FUEL LOADS) . |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | 2007 FL BUILDING CODE, EXISTING BUILDING, ADDING A |
| | MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED |
| | CHAPTERFOR ADDITIONS. |
| | B) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING) |
| | AS DEFINED IN CHAPTER 5, TABLE 503, CHAPTER 6, TABLE |
| | 601. |
| | C) PLANS INDICATE THERE IS A FIRE SPRINKLER SYSTEM, IS |
| | IT A REQUIRED SYSTEM FOR AREA INCREASES IN THE |
| | BUILDING? |
| | D) PLANS INDICATE THE OCCUPANCY TYPE TO BE A STORAGE |
| | OCCUPANCY, S1 OR S2? |
| | |
| | 3) THE PLAN INDICATES THE MEZZANINE LEVEL OCCUPANCY |
| | SHALL BE USED FOR STORAGE. |
| | |
| | 3A) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. |
| | IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| | AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| | SQ FT.THE |
| | COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT |
| | RECORD OF THE BLDG DEPT. |
| | |
| | 3B) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| | OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| | PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| | CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| | SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, |
| | REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. |
| | |
| | 4) NO PLANS WERE SUBMITTED FOR THE STRUCTURAL FRAMING |
| | OF THE MEZANINE NOR STAIRWAY OR FOR LOADING OF THE |
| | MEZZANINE LEVEL. |
| | 106.3.5 MINIUMUM PLAN CRITERIA FOR COMMERCIAL |
| | BUILDINGS. |
| | NOT HAVING BUILDING INFORMATION TYPE , FIRE RETARDANT |
| | CONSTRUCTION MAY ALSO BE A FACTOR WITH A PLYWOOD FLOOR. |
| | |
| | 5) PLANS INDICATE THE BUILDING HAS FIRE SPRINKLER |
| | SYSTEM ALREADY BUT NO PLANS WERE SUBMITTED FOR FIRE |
| | SPRINKLERS BENEATH THE MEZZANINE LEVEL. |
| | |
| | 6) GUARD RAILS, PLEASE PROVIDE COMPLIANCE WITH: |
| | 618.4.6.1 RAILINGS, STAIR-RAILINGS AND OTHER SIMILAR |
| | SAFEGUARDS SHALL BE DESIGNED TO RESIST A LOAD OF 50 |
| | POUNDS PER LINEAL FOOT (74 KG/M) OR A CONCENTRATED LOAD |
| | OF 200 POUNDS (690 N) APPLIED IN ANY DIRECTION AT THE |
| | TOP OF SUCH BARRIERS AT ANY LOCATION ON THE SAFEGUARD, |
| | WHICHEVER CONDITION PRODUCES THE MAXIMUM STRESSES. THE |
| | REACTIONS AND STRESSES CAUSED BY THE ABOVE REFERENCED |
| | UNIFORM AND CONCENTRATED LOADS SHALL BE CONSIDERED NOT |
| | BE ACTING SIMULTANEOUSLY. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE |
| | NOT PART OF THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |