| 2009-06-03 10:30:07 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC. |
| | THEREFORE, OWES $135.78. |
| | |
| | 3- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED |
| | FOR ROOF SHINGLES. NOA 05-1115.08 SUBMITTED EXPIRED ON |
| | 04/22/08. AND NOA 07-1120.14 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE COUNTY. SEE ATTACHED COPY FROM MIAMI DADE |
| | COUNTY WEBSITE. NEED TO PROVIDE TWO COPIES OF CURRENT |
| | SHINGLES PRODUCT APPROVAL. |
| | |
| | 4- COMMENTS TO FLAT ROOF NOA 09-0224.01 SUBMITTED: |
| | A) MARK WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED. |
| | |
| | B) MARK WHICH BASE SHEET FASTENING OPTION IS GOING TO |
| | BE INSTALLED. |
| | |
| | C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. |
| | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE |
| | USED IN THIS AREA. |
| | |
| | D) ACCORDING TO GENERAL LIMITATION #7 ON SHEET #31 OF |
| | NOA SUBMITTED, THE RAS 117 CALCULATIONS NEED TO BE |
| | SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. PROVIDE |
| | SIGNED AND SEALED CALCULATIONS. |
| | |
| | E) CLARIFY WHY THIS NOA WAS REVIEWED AND APPROVED BY |
| | THE ENGINEER LUIS LOPEZ. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |