2009-06-09 09:48:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EXHAUST FAN, DUCTWORK AND CURB SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12. PROVIDE MANUFACTURER'S DATA SHOWING THE FAN IS
 DESIGNED FOR WIND RESISTANCE. PROVIDE DETAIL FOR
 ATTACHMENT OF ROOF CURB TO BUILDING STRUCTURE, FAN TO
 ROOF CURB AND SUPPORT OF DUCT TO BUILDING STRUCTURE FOR
 WIND RESISTANCE.
  
 2. PLANS INDICATE THIS IS A VENTILATION SYSTEM FOR A
 GAS OVEN. WHERE APPLIANCES ARE VENTED THROUGH A
 VENTILATING HOOD OR EXHAUST SYSTEM EQUIPPED WITH A
 POWER MEANS OF EXHAUST, PROVISIONS SHALL BE MADE TO
 ALLOW THE FLOW OF GAS TO THE MAIN BURNERS ONLY WHEN THE
 POWER MEANS OF EXHAUST IS IN OPERATION IN ACCORDANCE
 WITH FBC-FG 503.3.4. SHOW MEANS OF INTERCONNECTION
 BETWEEN GAS SUPPLY AND EXHAUST FAN.
  
 3. PROVIDE "AIRFLOW SPECIALISTS, INC." CETTIFICATE OF
 AUTHORIZATION NUMBER IN THE ENGINEERING BUSINESS TITLE
 BLOCK IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 RULE 61G15-23.002.
  
 4. SEPARATE ELECTRICAL PERMIT REQUIRED TO PROVIDE POWER
 AND CONTROLS FOR THIS VENTILATION SYSTEM.
  