Plan Review Notes
Plan Review Notes For Permit 09060023
Permit Number 09060023
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-02-09 12:17:57*****DENIED*****
  
 THE FOLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET. ONLY NEWLY ADDED SHEET
 A-101 WAS CORRECTED
  
 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE
 SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE
 PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A
 GENERAL FIRE ALARM - IN ADDITION TO FAN SHUT DOWN.
 ADRRESS COMMENT
  
 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO
 REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101
 IS TO BE REFERENCED. ADDRESS COMMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722