| 2010-02-09 12:17:57 | *****DENIED***** | | | | | | THE FOLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. ONLY NEWLY ADDED SHEET | | | A-101 WAS CORRECTED | | | | | | 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE | | | SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE | | | PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A | | | GENERAL FIRE ALARM - IN ADDITION TO FAN SHUT DOWN. | | | ADRRESS COMMENT | | | | | | 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO | | | REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101 | | | IS TO BE REFERENCED. ADDRESS COMMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|