| 2010-01-26 14:58:31 | BUILDING PLAN REVIEW |
| | PERMIT: 09060023 |
| | ADD: 1009 BANYAN BLVD |
| | CONT: TO BE DETERMINED |
| | TEL: (561)659-2383 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | JAN. 26/2010 |
| | |
| | PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 |
| | |
| | |
| | 1) COMPLIED. |
| | |
| | 1A) 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1.1. COMPLIED. BASIC WIND SPEED (3-SECOND GUST), MILES |
| | PER HOUR (KM/HR). |
| | |
| | 1.2. 2ND REQUEST, WIND IMPORTANCE FACTOR, I W , AND |
| | BUILDING CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, |
| | ASCE 7 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE |
| | 7. |
| | PLEASE REVIEW THE BUILDING CATEGORIES, THIS BUILDING IS |
| | PART OF THE WATER DISTRIBUTION SYSTEM MAKING THIS A |
| | BUILDING CATEGORY IV OR A 1.15 IMPORTANCE FACTOR (TABLE |
| | 6-1). |
| | |
| | 1.3. COMPLIED. WIND EXPOSURE, IF MORE THAN ONE WIND |
| | EXPOSURE IS UTILIZED, THE WIND EXPOSURE AND APPLICABLE |
| | WIND DIRECTION SHALL BE INDICATED. |
| | |
| | 1.4.COMPLIED. THE APPLICABLE ENCLOSURE CLASSIFICATIONS |
| | AND, IF DESIGNING WITH ASCE 7, INTERNAL PRESSURE |
| | COEFFICIENT. |
| | |
| | 1.5. WITH THE 1.15 IMPORTANCE FACTOR THE STATED |
| | PRESSURES WILL BE LOW. COMPONENTS AND CLADDING. THE |
| | DESIGN WIND PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE |
| | USED FOR THE SELECTION OF EXTERIOR COMPONENTS AND |
| | CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 1B)PATIALLY COMPLIED. WITH THE NEW WIND PRESSURE |
| | COEFFICIENT PRESSURES WILL NEED TO BE REVIEWED WITH THE |
| | HIGHER PRESSURES. PROVIDE DOCUMENTATION ON THE WIND |
| | RESISTANT CURB. COMPONENTS AND CLADDING.1603.1.4(5). |
| | |
| | 2)) 2ND REQUEST, SHEET M-5 ALSO INDICATES THAT VARIOUS |
| | EXHAUST DUCTWORK IS BEING DELETED FROM PENETRTING THE |
| | ROOF, PLANS INDICATE TO PATCH HOLE,. THE RESPONSE |
| | INDICATES SHEET A1.01 DETAIL 1 WILL LEAVE THE CURBING. |
| | THE MECHANICAL PLANS MAKES ONE TO THINK THE CURB IS TO |
| | BE REMOVED! TO PATCH HOLE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |