| Plan Review Notes For Permit 09060023 |
| Permit Number |
09060023 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-26 10:42:35 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE | | | SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE | | | PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A | | | GENERAL FIRE ALARM - IN ADDITION TO FANN SHUT DOWN. | | | | | | 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO | | | REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101 | | | IS TO BE REFERENCED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|