Plan Review Notes
Plan Review Notes For Permit 09060023
Permit Number 09060023
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-26 10:42:35*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE
 SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE
 PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A
 GENERAL FIRE ALARM - IN ADDITION TO FANN SHUT DOWN.
  
 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO
 REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101
 IS TO BE REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722