| 2009-06-18 16:18:00 | BUILDING PLAN REVIEW |
| | PERMIT: 09060023 |
| | ADD: 1009 BANYAN BLVD |
| | CONT: TO BE DETERMINED |
| | TEL: (561)659-2383 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 |
| | |
| | |
| | 1) SHEET M-5 ROOF TOP UNITS, NOTES INDICATES THAT A |
| | STRUCTURAL ENGINEER WILL BE EMPLOYED TO VERIFY ROOF |
| | LOAD CAPACITY AND PROVIDE STRUCTURAL DETAILS FOR |
| | ADAPTION OF EXISTING ROOF OPENINGS FOR THE NEW ROOF |
| | CURBS. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 1A) 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 1B) PROVIDE DOCUMENTATION ON THE WIND RESISTANT CURB. |
| | COMPONENTS AND CLADDING.1603.1.4(5). |
| | |
| | 2)) SHEET M-5 ALSO INDICATES THAT VARIOUS EXHAUST |
| | DUCTWORK IS BEING DELETED FROM PENETRTING THE ROOF, |
| | PLANS INDICATE TO PATCH HOLE, PLEASE PROVIDE DETAILS AS |
| | TO HOW THIS WILL HAPPEN. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED, COMPONENTS AND |
| | CLADDING. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |