Plan Review Notes For Permit 09060020
Permit Number 09060020
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-31 12:07:22 
  
 ** DENIED 2ND REVIEW **
  
  
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW. PLEASE SUBMIT
 LIGHTING PERFORMANCE CALCULATIONS MEETING MINIMUM
 PRESCRIPTIVE REQUIREMENTS. THE ORIGINAL SUBMITTED
 CALCULATIONS WERE BASED ON METHOD *A* (WHOLE BUILDING)
 WHICH COULD NOT BE USED. THE NOTES STATED FOR NEW
 LIGHTING IN AREAS PER 13-415.AB.5. THERE ARE ONLY TWO
 METHODS OF CALCULATIONS NOW IN THE 2007 FBC W/2009
 REVISIONS. PREVIOUS REVIEW STATED METHOD *A* COULD NOT
 BE USED THIS WOULD LEAVE ONLY METHOD B.
 IT WAS STATED ON PREVIOUS REVIEW THAT IF THERE WERE ANY
 QUESTIONS TO PLEASE CALL THIS REVIEWER. THE RESPONSE
 FROM ARCHITECT STATES TO SEE MECHANICAL CONTRACTOR'S
 RESPONSE TO MECHANICAL REVIEW #4.
 THIS NOTES A CONVERSATION WITH RONALD REGUERIO
 MECHANICAL REVIEWER AND THAT *ENERGY CALCULATIONS* ARE
 NOT REQUIRED. ENERGY CALCULATIONS FOR MECHANICAL AND
 OTHER SYSTEMS MAY NOT BE REQUIRED HOWEVER MINIMUM
 LIGHTING PERFORMANCE CALCULATIONS ARE REQUIRED.
 13-400.0.B.4, 13-415.B, 13-415.B.1.
  
 ** A CALLED WAS PLACED TO ARCHITECT BY THIS REVIEWER TO
 TRY AND GO OVER COMMENT HOWEVER IT WAS NOT RECEIVED AS
 BEING PROACTIVE.
  
 2) NOTE: PLEASE SEE COMMENT #10 FROM PREVIOUS REVIEW.
 NO DEVICES, LOCATIONS, MINIMUMS FOR HEIGHTS OR ANY
 INFORMATION WAS SHOWN ON PLANS. PLEASE SHOW THE MINIMUM
 DEVICES MEETING ADA COMPLIANCE. PLACING A NOTE ON PLANS
 STATING DEVICES MUST MEET THE CODE SECTIONS IS NOT
 SHOWING ANY MINIMUM DESIGN.
 ** PLEASE CALL TO GO OVER. DOES THIS BUILDING CONTAIN
 AN EXISTING FIRE ALARM SYSTEM? IS ONE BEING INSTALLED?
 IF NO SYSTEM IS BEING INSTALLED OR REQUIRED THEN THIS
 NOTE CAN BE REMOVED.
 PLEASE ALSO CONTACT FIRE MARSHAL TO SEE IF REQUIRED.
  
 3) NOTE: MAINS WILL STILL BE REQUIRED TO BE LABLED PER
 230.2E. IE, MAIN ONE OF TWO ETC. THIS COULD BE
 REDLINED.
  
 *** PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER NEW
 BUILDING OFFICIAL.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  