| 2009-06-17 10:34:19 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. SHT A-1 SUBMIT A DETAIL FOR THE LOUNGE SINK (113). |
| | SHOWING COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH REQD) |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 2. SHT A-1 TOILET ROOM (108) SHALL BE ACCESSIBLE. |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.22 |
| | WITH ALL SUBSECTIONS. SECTIONS 11-4.1.3(11) & |
| | 11-4.1.6(1)(B). SHOW CLEAR FLOOR SPACE ON FLOOR PLAN AS |
| | WELL AS GRAB BARS. |
| | |
| | 3. SHT A-2 DETAIL 6/A-2 SHOW COMPLIANCE FOR THE |
| | FOLLOWING: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 4. SHT A-2 THE SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN IN TOILET ROOM 108. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 701.1. |
| | |
| | 5. SHT A-2 PLUMBING NOTES #7 AIR CHAMBERS ARE NOT |
| | APPROVED. PDI-WH 201. |
| | |
| | 6. SUBMIT A WATER ISOMETRIC RISER DIAGRAM. SHOW ALL |
| | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS ETC. SECTION |
| | 106.3.5.1.3(3)(8)(10)(13). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |