Plan Review Notes
Plan Review Notes For Permit 09060020
Permit Number 09060020
Review Stop P
Sequence Number 1
Notes
Date Text
2009-06-17 10:34:19DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-1 SUBMIT A DETAIL FOR THE LOUNGE SINK (113).
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH REQD)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 2. SHT A-1 TOILET ROOM (108) SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.22
 WITH ALL SUBSECTIONS. SECTIONS 11-4.1.3(11) &
 11-4.1.6(1)(B). SHOW CLEAR FLOOR SPACE ON FLOOR PLAN AS
 WELL AS GRAB BARS.
  
 3. SHT A-2 DETAIL 6/A-2 SHOW COMPLIANCE FOR THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
  
 4. SHT A-2 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN IN TOILET ROOM 108. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 701.1.
  
 5. SHT A-2 PLUMBING NOTES #7 AIR CHAMBERS ARE NOT
 APPROVED. PDI-WH 201.
  
 6. SUBMIT A WATER ISOMETRIC RISER DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS ETC. SECTION
 106.3.5.1.3(3)(8)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  