2009-07-06 15:01:04REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE SYSTEM SHALL BE PROVIDED WITH DUCT SMOKE
 DETECTOR IN ACCORDANCE WITH FBC-M 606.2.2.1. CONTROLS
 AND OPERATION SHALL COMPLY WITH FBC-M 606.3 AND 606.4.
  
 2. SHOW LOCATION OF BATHROOM EXHAUST TERMINATIONS IN
 ACCORDANCE WITH FBC-M 401.4 AND FBC-M 501.2.
  
 3. THE SPACE APPEARS TO BE DESIGNED WITH THE CEILING TO
 SERVE AS A RETURN AIR PLENUM. CEILING MOUNTED EXHAUST
 FANS WOULD RESULT IN POSITIVE PRESSURE EXHAUST DUCTS
 PASSING THROUGH THE RETURN AIR PLENUM. EXHAUST DUCTS
 UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH THE
 PLENUM IN ACCORDANCE WITH FBC-M 601.5.
  
 4. THE VENTILATION SCHEDULE INCLUDED IN THE COOLING
 LOAD CALCULATIONS CALL FOR A MINIMUM OF 50 CFM OF
 EXHAUST IN THE COPY ROOM. NO SUCH EXHAUST IS SHOWN ON
 THE PLANS. PLEASE COORDINATE PLANS WITH THE VENTILATION
 SCHEDULE.
  
 5. THE MECHANICAL PLANS SUBMITTED WERE DESIGNED BY AN
 AIR CONDITIONING CONTRACTOR. THE CONTRACTOR MAY ONLY
 ACT AS THE DESIGNER OF THIS SYSTEM IF THEY ARE ALSO THE
 INSTALLING CONTRACTOR. THIS REVIEW WILL REMAIN IN FAIL
 STATUS PENDING RECEIPT OF A PERMIT APPLICATION FOR THIS
 SCOPE OF WORK FROM NORTH COUNTY COOLING IN ACCORDANCE
 WITH FS 471.003
  