Plan Review Notes
Plan Review Notes For Permit 09060020
Permit Number 09060020
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-17 12:55:47** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES. STATING THE *LATEST EDITION*
 IS NOT ACCEPTABLE.
 FOR EXAMPLE, THE LATEST EDITION OF NFPA-70 NEC WHICH IS
 THE 2008 HAS NOT BEEN ADOPTED AS OF YET ALTHOUGH IT IS
 ALREADY OUT AND AVAILABLE. THE PLANS NEED TO STATE THE
 CODES IN THE DESIGN. SOME ARE SHOWN HOWEVER BE SURE ALL
 ARE SHOWN AS BELOW.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2005 FOR THIS CODE)
 2002 NFPA-72
 2006 NFPA-1
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: A *METHOD A* *WHOLE* BUILDING ENERGY
 CALCULATION WAS SUBMITTED. THE USE OF A WHOLE BUILDING
 CALCULATION WOULD BE JUST THAT, THE WHOLE BUILDING.
 THE CALCULATIONS AS SUBMITTED ARE NOT COMPLETE FOR
 WHOLE BUILDING.
 IN ANY CASE, ONLY NEW BEING INSTALLED NEEDS TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.AB.5
  
 3) NOTE: PLEASE SEE 422.13 AS ALL WATER HEATER LOADS
 SHALL BE FIGURED AT 125%. PLEASE SEE THE 2005 NEC AS
 THIS WAS A CHANGE WHICH WENT INTO AFFECT DECEMBER 8TH
 2006.
  
 4) NOTE: PLEASE LABEL ALL MAINS AS REQUIRED PER 230.2E.
 FOR EXAMPLE: MAIN 1 OF X, 2 OF X ETC.
  
 5) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. 408.4. PLEASE SEE
 COMMENTARY UNDER 2005 NEC HANDBOOK.
 ** IF THIS WAS THE ONLY COMMENT THIS COULD HAVE BEEN
 REDLINED.
  
 6) NOTE: PLEASE SHOW CODE COMPLIANCE FOR COMPLETE LOAD
 CALCULATIONS FOR PANEL LA. PANEL LA LOADS DO NOT SEEM
 TO INCLUDE LOADS FROM LB. BASED ON THE SHEETS SUBMITTED
 THE LOADS ARE ALL SHOWN SEPARATE AND THE LOADS AS SHOWN
 EXCEED THE 400AMP SERVICE ENTRANCE CONDUCTORS RATING
 PER 310.16.
 PLEASE SUBMIT AND SHOW COMPLETE LOAD CALCULATIONS FOR
 LA/LC. ( LB IS SHOWN FED FROM LA THEREFORE LB LOAD AS
 SHOWN FOR PANEL SHOULD BE FIGURED INTO THE LA LOAD.
 240.4,310.16, 220.12,220.14,220.42,220.44,ETC
 *** PLEASE KEEP IN MIND COMMENTS #3 ABOVE AS WELL AS
 ALL CONTINUOUS LOADS AT 125% ALONG WITH ANY LARGEST
 MOTOR LOADS.
 215.3,230.42
  
 7) NOTE: PLEASE SEE NOTE #4 ON PLANS WHICH STATES ALL
 LIGHTING CONTROLS SHALL BE PER 13-415.1.ABC.1.1, .1.2.
 THESE CODE SECTIONS HAVE BEEN REVISED UNDER THE NEW
 CODE. PLEASE SEE 13-415.AB.1.1,.1.2, .1.3.
  
 8) NOTE: PLEASE SEE FBC 13-413.AB.2.1, .2.2. PLEASE
 PLACE NOTES ON PLANS ACCORDINGLY. IT WAS CONFIRMED WITH
 THE STATE THAT THE VERBIAGE IN THE CODE IS THE INTENDED
 WORDING TO BE ON PLANS.
  
 9) NOTE: PLEASE PLACE NOTE FOR FIRE ALARM PANEL BRANCH
 CIRCUIT. THE BREAKER SHALL BE OF A LOCK ON/OFF TYPE
 BREAKER WHICH MEANS THE DEVICE SHALL BE AN INTEGRAL
 PART OF THE BREAKER. THE SNAP/CLICK ON TYPE DEVICES IS
 NOT ACCEPTABLE OR LISTED FOR THE PURPOSE. 110.3
 NFPA-72 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 10) NOTE: PLEASE SEE FBC 11-4.28.1, .2, .3 FOR MINIMUM
 DEVICES WHICH NEED TO BE SHOWN FOR ADA COMPLIANCE.
 PLEASE BE SURE TO ALSO SEE THE MINIMUM DEVICE HEIGHTS,
 LEVELS AND LOCATIONS NEED TO BE SHOWN ON PLANS.
 FS633.
 IF EXISTING, PLEASE SHOW LOCATIONS. THIS SPACE IS BEING
 RECONFIGURED FOR NEW TENANT SO THE LOCATIONS NEED TO BE
 VERIFIED.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  