| 2009-06-19 14:50:06 | BUILDING PLAN REVIEW |
| | PERMIT: 09060020 |
| | ADD: 5601 CORPORATE WAY # 400 |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561)719-3429 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 NOTES FOR BUILDING TYPE INDICATES TWO |
| | BUILDING TYPES A II AND V UNPROTECTED/ UNSPRINKLERED |
| | PLEASE PROVIDE BUILDING TYPE TABLE 503. |
| | |
| | 2) SHEET A-1 TENANT DEMISSING WALL EXISTING WALL SYMBOL |
| | INDICATES TO HAVE FIRE WALL RATING OVER EXISTING WALL |
| | WITH 2 LAYERS OF TYPE X BOARD ON ONE SIDE, PLEASE |
| | PROVIDE AN ASSEMBLY NUMBER FOR THIS CONFIGURATION. |
| | 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL |
| | HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | |
| | 3) PROVIDE TYPE OF FLEXIBLE FIRE PROOFING TO OCCUR AT |
| | THE ONE-HOURTENANT SEPERATION WALL AT ROOF DECK LEVEL. |
| | 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT |
| | CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE |
| | CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |