Plan Review Notes
Plan Review Notes For Permit 09060009
Permit Number 09060009
Review Stop E
Sequence Number 3
Notes
Date Text
2009-08-20 16:55:48*** REDLINED
  
  
 1) NOTE: RISER NOW REVISED TO REMOVE MAIN. EQUIPMENT
 GROUNDING CONDUCTOR STILL SHOWN BEFORE FIRST MEANS OF
 DISCONNECT. THIS IS NOT PERMITTED. 250.6, 250.24
  
 2) NOTE: VIF RECESSED LIGHTING MEETING FBC
 13-606.AB.1.2.4
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  