 PASSED/PROVISO:
 A REVISION IS REQUIRED FOR THE SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING THE CONNECTION OF THE BUILDING DRAIN TO
 THE BUILDING SEWER.
  
 SHT 5.1 PANEL BOARD SCHEDULE INDICATES A GAS RANGE &
 GAS INSTA-HOT WATER HEATER. A SEPARATE GAS PERMIT IS
 REQUIRED WITH GAS PLANS.
  
  
  
  
 .