2009-07-28 11:37:22REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NOT ADDRESSED: PLANS SHOW THE GARAGE BEING CONVERTED
 TO A BEDROOM. ANY EXPANSION OF THE CONDITIONED SPACE IS
 DEFINED AS AN ADDITION PER FBC-R SECTION N1100.7.3.
 ADDITIONS TO EXISTING RESIDENTIAL BUILDINGS SHALL BE
 CONSIDERED NEW BUILDING CONSTRUCTION AND SHALL COMPLY
 WITH THE REQUIREMENTS OF EITHER METHOD A OR B AS
 APPLICABLE PER FBC-R SECTION N1100.0.3. ADDITIONS THAT
 ARE UNABLE TO COMPLY WITH CODE REQUIREMENTS FOR THE
 ADDITION ALONE MAY COMPLY WITH THE CODE BY BRINGING THE
 ENTIRE BUILDING INTO COMPLIANCE WITH SECTION
 N1100.A.5.2.
  
 2. PARTIALLY ADDRESSED: NO MECHANICAL INFORMATION IS
 PROVIDED ON PLANS. PLEASE SHOW HOW EXISTING A/C SYSTEM
 IS TO BE MODIFIED OR WHAT NEW SYSTEM IS BEING INSTALLED
 FOR THE NEWLY CONDITIONED SPACE. AT A MINIMUM,
 COMPLIANCE WITH FBC-R303.8 MUST BE SHOWN ON PLANS.
 PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO ENERGY
 CALCULATIONS SHOWING EXISTING EQUIPMENT CAPABLE OF
 ADDITIONAL COOLING LOADS.
  
 3. PARTIALLY ADDRESSED: LOCATION OF BATH EXHAUST
 TERMINATION STILL NOT SHOWN ON PLANS.
  
 4. NEW PLANS NOW SHOW NEW GAS APPLIANCES BEING
 INSTALLED. THE FOLLOWING SHALL BE ADDRESSED:
 A. GAS DRYER: PROVIDE COMBUSTION AIR IN ACCORDANCE WITH
 FBC-R SECTION G2407.1 OR MAKEUP AIR IN ACCORDANCE WITH
 FBC-R SECTION G2439.4.
 B. PAGE 5.1 SHOWS ONE CARBON MONOXIDE DETECTOR LOCATED
 IN THE SITTING AREA. CARBON MONOXIDE ALARMS SHALL BE
 LOACTED WITHIN 10 FEET OF SLEEPING ROOMS IN ACCORDANCE
 WITH FBC-R313.4.
  
 5. PAGE AD.1 SHOWS A DETAIL FOR ROOF MOUNTED DUCT. THE
 PROPOSED DETAIL IS NOT CLEAR. IS THE DUCT SHOWN ON
 PLANS TO BE RUN ON THE ROOF? IF SO, WHY IS THE DUCT
 SHOWN ON THE PLANS ROUND WHILE THE SUPPORT DETAIL IS
 FOR RECTANGULAR DUCT? HOW CAN THERE BE EXISTING
 SLEEPERS ON A SECTION OF THE BUILDING WHICH WAS
 PREVIOUSLY UNCONDITIONED? PLEASE CLARIFY AND SHOW
 COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS OF
 FBC-R SECTION M1307.3.
  
 6. RETURN TRANSFER DUCTS ARE NOT SIZED TO MEET THE
 EXCEPTIONS UNDER FBC-R SECTION M1602.4. DESIGN RETURNS
 TO MEET THESE EXCEPTIONS OR A FIELD TEST WILL BE
 REQUIRED AT FINAL INSPECTION TO VERIFY MAXIMUM PRESSURE
 DIFFERENTIAL IN ACCORDANCE WITH THIS SECTION.
  