Plan Review Notes
Plan Review Notes For Permit 09060009
Permit Number 09060009
Review Stop E
Sequence Number 2
Notes
Date Text
2009-08-03 11:17:27** DENIED 2ND REVIEW **
  
 *** THERE ARE SEVERAL ITEMS ON PLANS NOW SHOWN WHICH
 WERE NOT ON PREVIOUS SUBMITTED PLANS. SOME OF THESE
 HAVE CREATED NEW COMMENTS WHICH COULD NOT HAVE BEEN
 PREVIOUSLY MADE.
 PANEL SCHEDULE AND EQUIPMENT ON PANEL HAS BEEN
 COMPLETELY REVISED.
  
 1) NOTE: ELECTRICAL RISER INDICATES A MAIN DISCONNECT
 AFTER METER, YET THIS IS NOT SHOWN ON THE PLANS. THE
 PLANS ONLY INDICATE THE PANEL AND THE METER.
 PANEL SCHEDULE INDICATES PANEL AS MLO. A MAIN WOULD BE
 REQUIRED EITHER AHEAD OF PANEL OR IN PANEL IF LOCATED
 PER 230.70,230.71,
 240.24,110.26 ETC
  
 2) NOTE: PREVIOUS PANEL SCHEDULE INDICATED A STORAGE
 TYPE WATER HEATER AND THE REVIEW COMMENT WAS TO SHOW
 LOAD AT 125%. THE PLANS ALSO INDICATED A INSTA-HOT.
 HOWEVER THE NEW PLANS ONLY INDICATES ONE *INSTA-HOT*
 LOCATED UNDER THE COUNTER IN THE BATHROOM AND PER THE
 PANEL SCHEDULE THIS IS NOW A GAS APPLIANCE.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR LOCATION.
 PLEASE ALSO EXPLAIN WHERE THE REMAINDER OF THE HOT
 WATER IS BEING FED FROM. IS THERE GOING TO BE ANOTHER
 GAS OR ELECTRIC WATER HEATING SOURCE?
 THERE ARE UNANSWERED QUESTIONS ON THIS AT THIS TIME.
 SEE 422.13, 220.87 ETC
  
 3) NOTE: PLEASE PREVIOUS PLANS WHICH PANEL SCHEDULE
 INDICATED A 101KW AHU WITH 2-60 ON #6AWG WHICH WAS OK.
 HOWEVER THE PANEL SCHEDULE NOW INDICATES THIS SAME AHU
 INDICATES AN EVEN HIGHER LOAD AT 12KW. THE OVER CURRENT
 PROTECTION IS LESS AND SMALLER BRANCH CIRCUIT
 CONDUCTORS ARE ALSO SHOWN. THESE DO NOT MEET 424.3B FOR
 MINIMUM OCP AND 310.16, 240.4 FOR BRANCH CIRCUIT
 CONDUCTORS.
 PLEASE SEE NEW AHU #2 AND #3 WHICH BOTH SHOW 40AMP OCP
 FOR TWO DIFFERENT HEAT LOADS. THIS DOES NOT SEEM
 POSSIBLE.
 MECHANICAL PLANS DO NOT GIVE ANY INFORMATION.
  
 4) NOTE: SAME AS PREVIOUS REVIEW: PLEASE IDENTIFY THE
 LIGHTING CONTROL SWITCHES WITH THE RESPECTIVE 3-WAY OR
 4-WAY DESIGNATION. THERE ARE MORE THAN ONE LOCATION
 STILL SHOWN. 210.70
  
 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING
 ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF
 INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE)
  
 6) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED
 TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE
 SURE TO UPDATE TYPE OF FIXTURES ON PLANS.
  
 7) NOTE: PLEASE SHOW LOCATION FOR THE NEW 30AMP
 RECEPTACLE FOR MICROWAVE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  