| 2009-08-03 11:17:27 | ** DENIED 2ND REVIEW ** |
| | |
| | *** THERE ARE SEVERAL ITEMS ON PLANS NOW SHOWN WHICH |
| | WERE NOT ON PREVIOUS SUBMITTED PLANS. SOME OF THESE |
| | HAVE CREATED NEW COMMENTS WHICH COULD NOT HAVE BEEN |
| | PREVIOUSLY MADE. |
| | PANEL SCHEDULE AND EQUIPMENT ON PANEL HAS BEEN |
| | COMPLETELY REVISED. |
| | |
| | 1) NOTE: ELECTRICAL RISER INDICATES A MAIN DISCONNECT |
| | AFTER METER, YET THIS IS NOT SHOWN ON THE PLANS. THE |
| | PLANS ONLY INDICATE THE PANEL AND THE METER. |
| | PANEL SCHEDULE INDICATES PANEL AS MLO. A MAIN WOULD BE |
| | REQUIRED EITHER AHEAD OF PANEL OR IN PANEL IF LOCATED |
| | PER 230.70,230.71, |
| | 240.24,110.26 ETC |
| | |
| | 2) NOTE: PREVIOUS PANEL SCHEDULE INDICATED A STORAGE |
| | TYPE WATER HEATER AND THE REVIEW COMMENT WAS TO SHOW |
| | LOAD AT 125%. THE PLANS ALSO INDICATED A INSTA-HOT. |
| | HOWEVER THE NEW PLANS ONLY INDICATES ONE *INSTA-HOT* |
| | LOCATED UNDER THE COUNTER IN THE BATHROOM AND PER THE |
| | PANEL SCHEDULE THIS IS NOW A GAS APPLIANCE. |
| | PLEASE SEE PLUMBING REVIEW COMMENTS FOR LOCATION. |
| | PLEASE ALSO EXPLAIN WHERE THE REMAINDER OF THE HOT |
| | WATER IS BEING FED FROM. IS THERE GOING TO BE ANOTHER |
| | GAS OR ELECTRIC WATER HEATING SOURCE? |
| | THERE ARE UNANSWERED QUESTIONS ON THIS AT THIS TIME. |
| | SEE 422.13, 220.87 ETC |
| | |
| | 3) NOTE: PLEASE PREVIOUS PLANS WHICH PANEL SCHEDULE |
| | INDICATED A 101KW AHU WITH 2-60 ON #6AWG WHICH WAS OK. |
| | HOWEVER THE PANEL SCHEDULE NOW INDICATES THIS SAME AHU |
| | INDICATES AN EVEN HIGHER LOAD AT 12KW. THE OVER CURRENT |
| | PROTECTION IS LESS AND SMALLER BRANCH CIRCUIT |
| | CONDUCTORS ARE ALSO SHOWN. THESE DO NOT MEET 424.3B FOR |
| | MINIMUM OCP AND 310.16, 240.4 FOR BRANCH CIRCUIT |
| | CONDUCTORS. |
| | PLEASE SEE NEW AHU #2 AND #3 WHICH BOTH SHOW 40AMP OCP |
| | FOR TWO DIFFERENT HEAT LOADS. THIS DOES NOT SEEM |
| | POSSIBLE. |
| | MECHANICAL PLANS DO NOT GIVE ANY INFORMATION. |
| | |
| | 4) NOTE: SAME AS PREVIOUS REVIEW: PLEASE IDENTIFY THE |
| | LIGHTING CONTROL SWITCHES WITH THE RESPECTIVE 3-WAY OR |
| | 4-WAY DESIGNATION. THERE ARE MORE THAN ONE LOCATION |
| | STILL SHOWN. 210.70 |
| | |
| | 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING |
| | ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF |
| | INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE) |
| | |
| | 6) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED |
| | TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE |
| | SURE TO UPDATE TYPE OF FIXTURES ON PLANS. |
| | |
| | 7) NOTE: PLEASE SHOW LOCATION FOR THE NEW 30AMP |
| | RECEPTACLE FOR MICROWAVE. |
| | |
| | |