| Plan Review Notes For Permit 09060009 |
| Permit Number |
09060009 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-19 11:03:28 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLANS SHOW THE GARAGE BEING CONVERTED TO A BEDROOM. | | | ANY EXPANSION OF THE CONDITIONED SPACE IS DEFINED AS AN | | | ADDITION PER FBC-R SECTION N1100.7.3. ADDITIONS TO | | | EXISTING RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW | | | BUILDING CONSTRUCTION AND SHALL COMPLY WITH THE | | | REQUIREMENTS OF EITHER METHOD A OR B AS APPLICABLE PER | | | FBC-R SECTION N1100.0.3. ADDITIONS THAT ARE UNABLE TO | | | COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE | | | MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE | | | BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. | | | | | | 2. NO MECHANICAL INFORMATION IS PROVIDED ON PLANS. | | | PLEASE SHOW HOW EXISTING A/C SYSTEM IS TO BE MODIFIED | | | OR WHAT NEW SYSTEM IS BEING INSTALLED FOR THE NEWLY | | | CONDITIONED SPACE. AT A MINIMUM, COMPLIANCE WITH | | | FBC-R303.8 MUST BE SHOWN ON PLANS. | | | | | | 3. SHOW LOCATION OF DRYER AND BATH EXHAUST TERMINATIONS | | | IN ACCORDANCE WITH FBC-R303.4, FBC-R303.5 AND FBC-R | | | SECTION M1501.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|