| 2009-06-18 15:57:37 | |
| | ** DENIED PLANS * |
| | |
| | 1) NOTE: PLEASE SEE FS 481.229, 471.003 AND 489 FOR |
| | REQUIRED DESIGN PROFESSIONAL. NO DESIGN PROFESSIONAL |
| | SHOWN. PLANS MUST BE DONE BY ONE OF THE SECTIONS GIVEN. |
| | |
| | 2) NOTE: PLEASE CLARIFY SHEETS SUBMITTED. NOTE THE FACT |
| | THAT THE ELECTRICAL SHEET 5.1 CLEARLY STATES *SHEET 8 |
| | OF 7* HOW IS THIS POSSIBLE? PLEASE COORDINATE ALL PLANS |
| | AND DOCUMENTS. |
| | |
| | 3) NOTE: PLEASE PROVIDE LAYOUT OF EXISTING DWELLING |
| | SHOWING NEW OR EXISTING SMOKE ALARMS MEETING CURRENT |
| | NFPA-72. PLEASE KNOW THAT PER FS 553.885 IF THE HOUSE |
| | HAS AN ATTACHED GARAGE OR GAS APPLIANCES ONE CARBON |
| | MONOXIDE DETECTOR IS REQUIRED. A SMOKE ALARM DEVICE CAN |
| | BE A COMBINATION DEVICE WITH THE CARBON MONOXIDE |
| | DETECTORS. |
| | IF EXISTING DOES NOT MEET CURRENT NFPA-72, THEN ALL |
| | MUST BE BROUGHT UP TO CODE. PLEASE KEEP IN MIND THE ARC |
| | FAULT PROTECTION PER 210.12 OF THE 2005 NEC. |
| | 11.8.3, 11.5.1.1, FBC R313.1 |
| | SMOKE ALARM TOO CLOSE TO BATHROOM DOOR 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD |
| | SHALL BE FIGURED AT 125% AS A CONTINUOUS LOAD. ( SEE |
| | NEC HANDBOOK). |
| | |
| | 5) NOTE: PLEASE COORDINATE THE PLANS WITH THE |
| | ELECTRICAL RISER AS SHOWN. PLANS ONLY INDICATE A METER |
| | LOCATED OUTSIDE WHEREAS THE RISER CLEARLY SHOWS A MAIN |
| | TO BE INSTALLED. |
| | RISER IS CONFUSING AS THE RISER INDICATES A NEW MAIN TO |
| | BE INSTALLED YET THE RISER IS ALSO NOTED AT *EXISTING*. |
| | WHICH IS IT? |
| | 110.26, 240.24, 230.70/71 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS. |
| | |
| | 6) NOTE: PLANS INDICATE THERE IS GOING TO BE A NEW |
| | INSTA-HOT HOWEVER THE PANEL SCHEDULE/LOAD CALCULATIONS |
| | AND PLUMBING PLANS DO NOT INDICATE ANY OF THIS? |
| | 408.4,240.4,310.16,220 ETC |
| | |
| | 7) NOTE: PLEASE IDENTIFY THE LIGHTING CONTROL SWITCHES |
| | WITH THE RESPECTIVE 3-WAY OR 4-WAY DESIGNATION. |
| | PLEASE ALSO SEE DOOR AREA OFF DINING ROOM WHICH THERE |
| | IS NO LIGHT ILLUMINATING THE EGRESS AREA. THERE ARE |
| | SEVERAL WAYS OF DOING THIS. PLEASE SHOW ONE *MINIMUM |
| | CODE REQUIRED* METHOD. |
| | 210.70 |
| | |
| | 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING |
| | ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF |
| | INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE) |
| | |
| | 9) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED |
| | TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE |
| | SURE TO UPDATE TYPE OF FIXTURES ON PLANS. |
| | |
| | 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS |
| | ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS SHALL BE |
| | FIGURED AT 1500VA FOR EACH. PLANS SHOW THE TWO MINIMUM |
| | KITCHEN SMALL APPLIANCES HOWEVER THE 1500VA IS FOR EACH |
| | INCLUDING AND ABOVE THE TWO. FOR EXAMPLE: DINING ROOM, |
| | AND AREAS OF THE LIKE. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |