Plan Review Notes
Plan Review Notes For Permit 09060009
Permit Number 09060009
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-18 15:57:37 
 ** DENIED PLANS *
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003 AND 489 FOR
 REQUIRED DESIGN PROFESSIONAL. NO DESIGN PROFESSIONAL
 SHOWN. PLANS MUST BE DONE BY ONE OF THE SECTIONS GIVEN.
  
 2) NOTE: PLEASE CLARIFY SHEETS SUBMITTED. NOTE THE FACT
 THAT THE ELECTRICAL SHEET 5.1 CLEARLY STATES *SHEET 8
 OF 7* HOW IS THIS POSSIBLE? PLEASE COORDINATE ALL PLANS
 AND DOCUMENTS.
  
 3) NOTE: PLEASE PROVIDE LAYOUT OF EXISTING DWELLING
 SHOWING NEW OR EXISTING SMOKE ALARMS MEETING CURRENT
 NFPA-72. PLEASE KNOW THAT PER FS 553.885 IF THE HOUSE
 HAS AN ATTACHED GARAGE OR GAS APPLIANCES ONE CARBON
 MONOXIDE DETECTOR IS REQUIRED. A SMOKE ALARM DEVICE CAN
 BE A COMBINATION DEVICE WITH THE CARBON MONOXIDE
 DETECTORS.
 IF EXISTING DOES NOT MEET CURRENT NFPA-72, THEN ALL
 MUST BE BROUGHT UP TO CODE. PLEASE KEEP IN MIND THE ARC
 FAULT PROTECTION PER 210.12 OF THE 2005 NEC.
 11.8.3, 11.5.1.1, FBC R313.1
 SMOKE ALARM TOO CLOSE TO BATHROOM DOOR 11.8.3
  
 4) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD
 SHALL BE FIGURED AT 125% AS A CONTINUOUS LOAD. ( SEE
 NEC HANDBOOK).
  
 5) NOTE: PLEASE COORDINATE THE PLANS WITH THE
 ELECTRICAL RISER AS SHOWN. PLANS ONLY INDICATE A METER
 LOCATED OUTSIDE WHEREAS THE RISER CLEARLY SHOWS A MAIN
 TO BE INSTALLED.
 RISER IS CONFUSING AS THE RISER INDICATES A NEW MAIN TO
 BE INSTALLED YET THE RISER IS ALSO NOTED AT *EXISTING*.
 WHICH IS IT?
 110.26, 240.24, 230.70/71
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: PLANS INDICATE THERE IS GOING TO BE A NEW
 INSTA-HOT HOWEVER THE PANEL SCHEDULE/LOAD CALCULATIONS
 AND PLUMBING PLANS DO NOT INDICATE ANY OF THIS?
 408.4,240.4,310.16,220 ETC
  
 7) NOTE: PLEASE IDENTIFY THE LIGHTING CONTROL SWITCHES
 WITH THE RESPECTIVE 3-WAY OR 4-WAY DESIGNATION.
 PLEASE ALSO SEE DOOR AREA OFF DINING ROOM WHICH THERE
 IS NO LIGHT ILLUMINATING THE EGRESS AREA. THERE ARE
 SEVERAL WAYS OF DOING THIS. PLEASE SHOW ONE *MINIMUM
 CODE REQUIRED* METHOD.
 210.70
  
 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING
 ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF
 INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE)
  
 9) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED
 TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE
 SURE TO UPDATE TYPE OF FIXTURES ON PLANS.
  
 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS
 ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS SHALL BE
 FIGURED AT 1500VA FOR EACH. PLANS SHOW THE TWO MINIMUM
 KITCHEN SMALL APPLIANCES HOWEVER THE 1500VA IS FOR EACH
 INCLUDING AND ABOVE THE TWO. FOR EXAMPLE: DINING ROOM,
 AND AREAS OF THE LIKE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  