| 2009-06-16 11:52:52 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.0 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) FRENCH DOORS INCLUDING FRENCH DOORS WITH SIDELITES |
| | AS SHOWN ON PLANS. |
| | |
| | B) FIXED WINDOWS AS SHOWN ON PLANS. |
| | |
| | C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| | |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | ON DRAWINGS SPECIFIC MULLION SIZE AND ANCHORS TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. SEC. |
| | R301. |
| | |
| | E) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT |
| | GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | SEE ATTACHED SAMPLE. IN ADDITION MARK ON DRAWINGS |
| | SHUTTERS MOUNTING CONDITIONS AND ANCHOR TYPE AND |
| | SPACING TO BE USED. |
| | |
| | F) PRECAST LINTELS AS SHOWN ON PLANS. |
| | |
| | G) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS |
| | AND DETAILS. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 5- SHEET 3.1: |
| | A) SPECIFY SAFETY GLASS FOR WINDOW ON SHOWER OF MASTER |
| | BATHROOM AND WINDOWS NEXT TO SWING DOOR IN MASTER |
| | BEDROOM. SEC. R308.4 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE EGRESS WINDOWS NOTE: SEE SEC. R310 OF 2007 |
| | FLORIDA RESIDENTIAL CODE FOR CORRECT MIN. OPENING |
| | HEIGHT AND CORRECT MIN. NET CLEAR OPENING. |
| | |
| | C) INFORMATION ON WIND DESIGN INFORMATION AND DESIGN |
| | PARAMETERS DON'T CORRESPOND TO EACH OTHER. ONE CALLS |
| | FOR BUILDING EXPOSURE "C", WHILE THE OTHER ONE CALLS |
| | FOR BUILDING EXPOSURE "B". REVISE AS REQUIRED TO MATCH. |
| | (NOTE: ACCORDING TO 2009 REVISIONS, BUILDING IS LOCATED |
| | ON EXPOSURE "C"). |
| | |
| | D) REVISE CODE SECTIONS SPECIFIED ON WIND DESIGN |
| | INFORMATION AND DESIGN PARAMETERS INFORMATION. SEE FBC |
| | 2007 FOR CORRECT SECTION TO BE REFERENCED AND REVISE AS |
| | REQUIRED. |
| | |
| | E) FRAMED WALLS REQUIRES TWO LAYERS OF WATER RESISTANT |
| | BARRIERS AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. REVISE GENERAL WALL LEGEND AS |
| | REQUIRED. |
| | |
| | F) SPECIFY MIN. STUCCO THICKNESS (7/8") AS REQUIRED BY |
| | TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE. |
| | REVISE GENERAL WALL LEGEND AS REQUIRED. |
| | |
| | G) CLARIFY WHY THERE IS A NOTE THAT IMPACT RESISTANT |
| | WINDOWS REQUIRE 2X BUCKS. SEE WINDOW PRODUCT APPROVAL |
| | AND REVISE/CLARIFY AS REQUIRED. |
| | |
| | 6- SHEET 4.1: |
| | A) REVISE TYPICAL DOOR JAMB DETAIL. 2X4 STRUCTURAL BUCK |
| | SIZE DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME AS |
| | REQUIRED BY SEC. R613.6 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. SEE DOOR PRODUCT APPROVAL FOR SIZE OF FRAME AND |
| | SPECIFIED CORRECT STRUCTURAL BUCK SIZE. |
| | |
| | B) TYP. WOOD WALL SECTION: SPECIFY 2 LAYERS OF WATER |
| | RESISTANT BARRIER (SEC. R703.6.3) AND MIN. STUCCO |
| | THICKNESS (TABLE R702.1(1). |
| | |