| 2009-07-04 12:10:18 | |
| | ** DENIED PLANS 2ND REVIEW ** |
| | SOME NOTES FROM PREVIOUS REVIEW STILL NOT ADDRESSED. |
| | SOME NEW NOTES BASED ON SOME INFORMATION SHOWN NOT ON |
| | PREVIOUS PLANS. |
| | AS STATED ON PREVIOUS REVIEW, IF THERE ARE QUESTIONS OR |
| | COMMENTS OR IF THERE ARE ANY NOTES NOT TYPED IN A CLEAR |
| | MANNER PLEASE CALL. NO CONTACT WAS MADE FROM LAST |
| | REVIEW AND IT APPEARS PERHAPS SOME NOTES WERE NOT |
| | UNDERSTOOD. |
| | |
| | 1) NOTE: AS THE SCALE IS VERY SMALL AND THERE IS A LOT |
| | OF ITEMS SHOWN ON PLANS. AS STATED ON PREVIOUS REVIEW |
| | PLANS ARE CONGESTED. CIRCUITING IS NOT CLEAR. SOME |
| | ITEMS STILL DO NOT INDICATE CIRCUITING. SEE REDLINED |
| | PLANS. OTHERS SUCH AS CIRCUIT 2A, 9B, 7B AND 12A ARE |
| | STATED AS GENERAL LIGHTING. PLEASE SEE COMMENTARY FROM |
| | THE 2005 NEC IN 408.4. THESE NEED TO BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. LIVING ROOM |
| | LTS/RECEPTS, KITCHEN LIGHTS ETC OR OTHER DESIGNATION. |
| | 408.4, 210.52, 210.11 ETC |
| | |
| | 2) NOTE: MINIMUM OF TWO SMALL APPLIANCE CIRCUITS IS |
| | REQUIRED PER 210.52B1, 210.11C1, 220.53. LIGHTING |
| | CIRCUIT 7B IS SHOWN CONNECTED TO RECEPTACLE IN ONE AREA |
| | WHICH IS NOT PERMITTED. |
| | THE KITCHEN PLANS ARE NOT CLEAR. |
| | |
| | 3) NOTE: PLEASE SEE GUEST BATH. THIS ROOM SHOWS THE |
| | CIRCUIT TO GFI AS 5B. THIS IS SHOWN AS A BEDROOM |
| | CIRCUIT ON PANEL SCHEDULE WITH #14AWG AND 15AMP |
| | BREAKER. THIS IS NOT PERMITTED. PLEASE SEE 210.11C3 AS |
| | BATH GFI CIRCUITS/RECEPTACLES ARE ONLY PERMITTED TO BE |
| | CIRCUITED ONE OF TWO WAYS. IN EITHER CASE THEY ARE ALSO |
| | REQUIRED TO BE 20AMP AND #12. |
| | |
| | 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE |
| | MISSING FOR WALL SPACES. SEE ONE SET OF PLANS WHICH ARE |
| | REDLINED. |
| | WALL IN MASTER BEDROOM, WALL IN OTHER GUEST ROOM. |
| | |
| | 5) NOTE: PLEASE SEE S1 AND S2 NOTES ON PLANS. THE |
| | SYMBOL LEGEND STATES S 1 AND S2 ARE SMOKE ALARMS, YET |
| | THE NOTES STATE S2 IS A SMOKE DETECTOR WHICH IS NOT THE |
| | SAME. S2 NOTE ALSO STATES ONLY TO BE INTERCONNECTED |
| | WHEN WITHIN 20FT OF COOKING APPLIANCES. |
| | |
| | A) ALL SMOKE DETECTION DEVICES WHETHER OR NOT SMOKE |
| | ALARMS OR DETECTORS ARE REQUIRED TO BE INTERCONNECTED |
| | IN THIS R OCCUPANCY. |
| | B) ALL SHALL BE CIRCUITED SINGLE STATION INTERCONNECTED |
| | AND ON ONE OF THE ARC FAULT PROTECTED CIRCUITS PER |
| | 210.12. SINCE S2 OUTSIDE SLEEPING ROOM IS REQUIRED TO |
| | BE INTERCONNECTED WITH THE S1 UNITS, THIS MUST ALSO BE |
| | ON THE SAME AFCI CIRCUIT. |
| | |
| | NFPA-72 11.8.3,11.5.1, NEC 210.12. |
| | |
| | |
| | |
| | ** ONLY NOTED FOR INFORMATION. LOW VOLTAGE SHOWN ON |
| | PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT. MAY |
| | USE THESE PLANS AS A REFERENCE FOR TURN AROUND PERMIT. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |