| 2009-06-17 15:16:45 | |
| | |
| | |
| | |
| | ** DENIED PLANS * |
| | |
| | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| | FOLLOWING MINIMUM CODES. |
| | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| | PLANS. |
| | 2007 FBC W/ 2009 AMENDMENTS. |
| | 2006 NFPA-101 ( PLANS STATE 2003 FOR THIS CODE) |
| | 2002 NFPA-72 |
| | 2006 NFPA-1 |
| | 2005 NFPA-70 ( PLANS DO NOT GIVE YEAR) |
| | |
| | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| | |
| | 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WITHOUT THE |
| | MECHANICAL SHADED OVER THE ELECTRICAL DETAILS. SOME |
| | ITEMS ARE NOT CLEAR TO BE REVIEWED FOR CODE COMPLIANCE. |
| | THE KITCHEN PLANS FOR EXAMPLE ARE VERY CONGESTED AND |
| | NOT EASILY READ FOR CODE COMPLIANCE VERIFICATION OF |
| | 210.52C1-5 FOR EXAMPLE. |
| | FBC 106.1.1 FOR CLARITY AND QUALITY OF SUBMITTED PLANS. |
| | NEC, 300,210,ETC |
| | |
| | 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| | DETECTION DEVICES. PER THE SYMBOL LEGEND THE PLANS |
| | STATE THERE IS GOING TO BE SMOKE DETECTORS. SMOKE |
| | DETECTORS ARE DEVICE WHICH DETECT HOWEVER DO NOT SOUND |
| | AN ALARM. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE |
| | SUBMIT MORE DETAILS ON THE COMPLETE SYSTEM SHOWING THE |
| | HORNS, STROBES PANEL OR SOUNDING DEVICES TO ALERT THE |
| | OCCUPANT. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | ** PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE ALARMS. IF |
| | THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AN ALARM |
| | PLEASE ADJUST PLANS ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE BE SURE TO SEE 210.4B FOR ANY DEVICES |
| | OR SINGLE YOKE BEING FED FROM MORE THAN ONE CIRCUIT. |
| | THIS MAY BE THE DISHWASHER/DISPOSAL WHICH WOULD REQUIRE |
| | A TWO POLE BREAKER. IT IS NOT CLEAR AT THIS TIME IF |
| | THIS IS THE SAME YOKE OR NOT. |
| | |
| | 5) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOAD UNDER |
| | THE 2005 NEC IS NOW CONSIDERED A CONTINUOUS LOAD WHICH |
| | REQUIRES 125% TO BE FIGURED INTO THE CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON THE |
| | LOAD CALCULATIONS ARE NOT FROM THE CURRENT EDITION OR |
| | EVEN PREVIOUS EDITION OF THE NEC. IN FACT PLANS STATE |
| | 202.32, 202.30. THERE IS NO SECTION 202 LOCATED IN |
| | NFPA70. EVEN IF THESE WERE MISPRINTS TO BE |
| | 220.30,220.32, THE CURRENT EDITION OF THE NEC WHICH IS |
| | THE ADOPTED 2005 DOES NOT CONTAIN THESE SECTIONS. |
| | PLEASE SEE NEW CODE WHICH WENT INTO AFFECT DECEMBER 8TH |
| | 2006. |
| | |
| | 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS EACH |
| | OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS SHALL BE |
| | FIGURED AT 1500VA FOR EACH. NO LOAD IS SHOWN IN THE |
| | LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLE |
| | CIRCUIT. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |