| Plan Review Notes For Permit 09050568 |
| Permit Number |
09050568 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-10-16 12:35:36 | ** PROVISO ** | | | | | | PROVISO FROM PREVIOUS REVIEW NOT ADDRESSED. | | | | | | | | | 1) NOTE: CONDENSATE PUMPS ARE LABELED AS CIRCUIT L-8, | | | ALTHOUGH THERE IS NO L PANEL. THE PANEL SCHEDULE | | | INDICATES L-14 TYPICAL. | | | 408.4 | | | | | | 2) NOTE: LIGHTING CONTROLS FOR ROOMS 109,110, AND 111 | | | STILL REQUIRED TO MEET FBC 13-415.AB.1.1,.1.2 FOR | | | MINIMUM PRESCRIPTIVE. | | | | | | 3) NOTE: REDLINED PLANS, NO CORDS ARE PERMITTED ABOVE | | | CEILING FOR CONDENSATE PUMPS. 400.8(2). | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|