Plan Review Notes
Plan Review Notes For Permit 09050568
Permit Number 09050568
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-17 16:15:28 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE.
 AN EXAMPLE WOULD BE OFFICE 107 AS THE DESIGN ALLOWANCE
 IS OVER.
 PLEASE ALSO SEE RECEPTION AREA. THESE ARE DEFINED AS
 TWO SPACES ALTHOUGH SHOWN IN CALCULATIONS AS ONE.
 ANOTHER WOULD BE HALL AND SUPPLY WHICH ARE SHOWN
 FIGURED AS THE SAME SPACE HOWEVER THESE ARE CLEARLY
 SEPARATE SPACES ON TABLE.
 PLEASE ADJUST.
 HALLWAY SHOWS THE ADDITION OF A FIXTURE HOWEVER NO
 CIRCUIT, CONTROLS OR INFORMATION IS NOTED. PLEASE ALSO
 KNOW THAT ADDITIONAL LIGHTING MAY NOT BE ADDED IF THE
 EXISTING ALREADY EXCEEDS THE ALLOWANCE.
 ** ALLOWANCES FOR ROOMS SUCH AS ROOMS 109 AND 110 EVEN
 EXCEED ALLOWANCES UNDER THE 2001 CODE.
  
 3) NOTE: PLEASE CONFIRM THE ADDRESS LOCATION. THE
 APPLICATION NEEDS TO STATE WHETHER OR NOT THIS IS FOR
 EAST OR WEST TOWER OR CORRECT SUITE/UNIT. FOR EXAMPLE
 THE ELECTRICAL RISER SHOWS THE NEW METER AND MAIN TO
 NEW SUITE #1500 WHICH ALSO CONTAINS THE METER AND MAIN
 TO A SUITE #200. IF THIS IS BEING FED FROM SECOND FLOOR
 UP TO 15TH FLOOR HEN MORE INFORMATION IS NEED FOR
 CONDUCTOR SUPPORTS IN 300.19, VOLTAGE DROP IN 13-413 OF
 THE FBC.
 FBC 106.5
  
 4) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  