Plan Review Notes
Plan Review Notes For Permit 09050559
Permit Number 09050559
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-29 13:43:03RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- FLAT ROOF:
 A) SELECTED ASSEMBLY ON SHEET 17 OF NOA 07-1219.09
 SUBMITTED IS GOOD FOR -52.5PSF MAXIMUM DESIGN
 PRESSURES. THIS BUILDING IS LOCATED IN AN AREA THAT
 REQUIRES HIGHER DESIGN PRESSURES FOR PERIMETER AND
 CORNER AREAS. THEREFORE, NAIL ENHANCING AS REQUIRED BY
 GENERAL LIMITATION #7 ARE REQUIRED.
  
 B) GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED
 REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED
 BY ANY OF THE DESIGN PROFESSIONAL LISTED. SEE GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS.
 ***NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION
 THAT ACCORDING TO THE 2009 REVISIONS TO THE 2007
 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED ON
 EXPOSURE C, NOT B. SEE REVISIONS TO BUILDING EXPOSURE
 ON SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- SHINGLES PRODUCT APPROVAL 07-1120.14 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE COUNTY. SEE ATTACHED COPY FROM
 MIAMI-DADE COUNTY WEBSITE. NEED TO PROVIDE CURRENT NOA
 08-1110.09 WHICH SUPERSEDES NOA 07-1120.14.
  
 3- COBRA VENTILATION NOA 08-0826.02 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE COUNTY ALSO. SEE ATTACHED
 COPY. PROVIDE CURRENT NOA 09-0105.08.
  