| Plan Review Notes For Permit 09050550 |
| Permit Number |
09050550 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-02 09:56:03 | 2007 FBC | | | REVISION TO INCREASE SCOPE OF DEMO PERMIT | | | | | | DENIED BY BUILDING | | | | | | 1) PROVIDE TWO COPIES OF A SITE PLAN SHOWING THE FOOT | | | PRINT OF THE ENTIRE BUILDING IN RELATION TO THE | | | PROPERTY LINE AND THE LOCATION OF THE UNITS INVOLVED IN | | | THE SCOPE OF WORK. FBC 106.1.1 | | | | | | 2) THE REVISED DEMO PLAN INDICATES WORK INVOLVING A | | | CORRIDOR THAT MAY BE A REQUIRED MEANS OF EGRESS FOR | | | OTHER AREAS OF THE MULTI-STORY BUILDING. PROVIDE TWO | | | COPIES OF A KEY PLAN SHOWING THE MEANS OF EGRESS FROM | | | THE ADJACENT UNITS AND UPPER FLOORS. FBC 1003 | | | | | | 3) THE REMOVAL OF THE EXTERIOR STORE FRONTS CAN BE | | | "PROVISO-ED" SO THAT THEY CAN NOT BE REMOVED UNTIL A | | | PERMIT HAS BEEN ISSUED FOR THE SYSTEM THAT WILL BE | | | INSTALLED TO REPLACE THEM. | | | | | | 4) THE SCOPE OF WORK IS BEING INCREASED, THEREFORE, THE | | | VALUE OF THE WORK NEEDS TO BE INCREASED AND ADDITIONAL | | | PERMIT FEES PAID BEFORE THE REVISION CAN BE APPROVED. | | | PLEASE INDICATE THE VALUE OF THE ADDITIONAL WORK. FBC | | | 108.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|