Plan Review Notes
Plan Review Notes For Permit 09050494
Permit Number 09050494
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-28 09:25:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
  
 1. S3, LADDER FRONT STATES THAT RUNG SPACING IS 10"MIN
 AND 8"MAX, PLEASE CLARIFY DESIGN CRITERIA FBC1509.
  
 2. FBC1509.6(4) LADDER WIDTH IS TO BE 18" BETWEEN RAILS
 MINIMUM (16" SHOWN).
  
 3. FBC1509.6(6), INDICATE LADDER HEIGHT.
  
 4. ROOF PERMIT MAY BE REQUIRED; INFORMATION REGARDING
 PRODUCT APPROVALS (MATERIAL PROPOSED) AND ENHANCED
 FASTENING WILL BE REQUIRED. THIS MAY BE DONE EITHER NOW
 OR AT TIME OF ROOF PERMIT APPLICATION. TO AVOID FIELD
 DELAYS, CONTRACTOR IS ENCOURAGED TO ADDRESS THIS ISSUE
 AT THIS TIME. S2 ROOF PITCH POCKET DETAIL STATES THAT
 NEW ROOFING MATERIAL WILL BE INSTALLED 36" BEYOND AREA
 OF WORK. PLEASE DECLARE ROOF COMPONENT & CLADDING
 PRESSURES FBC1603.1.4(5). IT APPEARS THAT THE ROOFING
 WORK PROPOSED WILL BE IN ZONE 3; PLEASE CONFIRM.
  
 5. LADDER RUNGS TO WITHSTAND 300# LOAD, FBC1509.6(5).
 CALCULATIONS ARE FOR 200#, PLEASE CLARIFY.
  
 6. LADDER CALCS, MAX MOMENT INCLUDES A 1.3333 FACTOR;
 PLEASE EXPLAIN SOURCE OF THIS NUMBER.
  
 6. GUARDS ARE TO COMPLY WITH FBC1607.7, PLEASE NOTE
 DESIGN CRITERIA FOR GUARDRAILS ON THE PLAN.
 CALCULATIONS INCLUDE 200# CONCENTRATED BUT COMPLIANCE
 WITH 50PLF WAS NOT CLEAR.
  
 7. EQUIPMENT LADDERS ARE TO COMPLY WITH FBC1509.6;
 PLEASE CHECK ALL REQUIREMENTS AND CONFIRM COMPLIANCE.
 PLEASE STATE COMPLIANCE WITH DESIGN CRITERIA FOR LADDER
 RUNGS (COMMENT 5), GUARDS (COMMENT 6), AND FBC1509.6 ON
 THE PLAN.
  
 8. S3 STATES THAT OSHA REQUIREMENTS PREVAIL OVER THE
 DRAWINGS. DESIGN CRITERIA SHOULD AT A MINIMUM CONFORM
 WITH FBC2007; IN THE EVENT OF CONFLICT, SHOULDN'T THE
 MORE STRINGENT PREVAIL? PLEASE NOTE THAT FOR BUILDING
 CODE PURPOSES, FBC2007 SHALL BE MINIMUM CRITERIA BUT
 OTHER REGULATIONS NOT ENFORCED BY THIS DEPARTMENT MAY
 ALSO APPLY.
  
 9. CALCULATIONS INCLUDE FBC R301.7, ALLOWABLE
 DEFLECTION OF STRUCTURAL MEMBERS, THIS APPLIES TO R3
 OCCUPANCY (TABLE IS FROM FBC RESIDENTIAL).
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved