| Plan Review Notes For Permit 09050486 |
| Permit Number |
09050486 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-27 11:55:42 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. PLANS NOW CALL FOR 3" ROUND DRYER EXHAUST. IF THIS | | | SIZE IS CORRECT, PLEASE SUBMIT MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS IN ACCORDANCE WITH FBC-R | | | SECTION M1502.3. OTHERWISE, PLEASE SHOW THE STANDARD 4" | | | ROUND SIZE. | | | | | | 5. ENERGY CALCULATIONS HAVE BEEN SUBMITTED, HOWEVER | | | THEY DO NOT ACCURATELY REFLECT THE HOME CONSTRUCTION. | | | THIS PROJECT IS NOT ELIGIBLE FOR THE WHOLE HOUSE FAN | | | CREDIT IN ACCORDANCE WITH FBC-R SECTION N1107.A.6. | | | RESUBMIT ENERGY CALCULATIONS WITHOUT THE WHOLE HOUSE | | | FAN CREDIT. ALSO, COOLING LOAD CALCULATIONS SHALL BE | | | ATTACHED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH | | | FBC-R SECTION N1107.AB.1. | | | | | | 6. OK | | | | | | 7. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|