2009-07-27 11:55:42REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. PLANS NOW CALL FOR 3" ROUND DRYER EXHAUST. IF THIS
 SIZE IS CORRECT, PLEASE SUBMIT MANUFACTURER'S
 INSTALLATION INSTRUCTIONS IN ACCORDANCE WITH FBC-R
 SECTION M1502.3. OTHERWISE, PLEASE SHOW THE STANDARD 4"
 ROUND SIZE.
  
 5. ENERGY CALCULATIONS HAVE BEEN SUBMITTED, HOWEVER
 THEY DO NOT ACCURATELY REFLECT THE HOME CONSTRUCTION.
 THIS PROJECT IS NOT ELIGIBLE FOR THE WHOLE HOUSE FAN
 CREDIT IN ACCORDANCE WITH FBC-R SECTION N1107.A.6.
 RESUBMIT ENERGY CALCULATIONS WITHOUT THE WHOLE HOUSE
 FAN CREDIT. ALSO, COOLING LOAD CALCULATIONS SHALL BE
 ATTACHED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH
 FBC-R SECTION N1107.AB.1.
  
 6. OK
  
 7. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: