| 2009-06-04 14:37:44 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. UPDATE ALL CODE REFERENCES ON PLANS TO REFLECT THE |
| | CODE IN EFFECT AT TIME OF PERMIT APPLICATION. THE |
| | CURRENT CODE AS OF MARCH 1, 2009 IS THE 2007 FBC W/ |
| | 2009 SUPPLEMENT. |
| | |
| | 2. A MECHANICAL PERMIT HAS BEEN APPLIED FOR BUT NO |
| | MECHANICAL PLANS WERE PROVIDED FOR THIS REVIEW. PROVIDE |
| | PLAN SHOWING IN DETAIL THE MECHANICAL SCOPE OF WORK IN |
| | ACCORDANCE WITH FBC-B 106.1.1. |
| | |
| | 3. ELECTRICAL PLAN SHOWS NEW EXHAUST FAN IN BATHROOM. |
| | SHOW SIZE OF DUCT AND EXHAUST TERMINATION LOCATION IN |
| | ACCORDANCE WITH FBC-R SECTION M1501.1. |
| | |
| | 4. SHOW MEANS AND LOCATION OF DRYER EXHAUST IN |
| | ACCORDANCE WITH FBC-R SECTION M1502. |
| | |
| | 5. NO ENERGY CALCULATIONS WERE PROVIDED AS PART OF THIS |
| | REVIEW. ANY INCREASE IN THE CONDITIONED FLOOR AREA IS |
| | CONSIDERED AN ADDITION IN ACCORDANCE WITH FBC-R SECTION |
| | N1100.7. ADDITIONS SHALL BE TREATED AS NEW CONSTRUCTION |
| | AND SHALL DEMONSTRATE COMPLIANCE BY SUBMITTING FORM |
| | 1100A-08 OR FORM 1100B-08 IN ACCORDANCE WITH FBC-R |
| | SECTION N1100.0.3. THIS BUILDING IS NOT EXEMPT FROM |
| | ENERGY EFFICIENCY REQUIREMENTS AS THE ELECTRICAL SYSTEM |
| | HAS BEEN DESIGNED TO ACCOMMODATE THE FUTURE |
| | INSTALLATION OF HEATING OR COOLING EQUIPMENT IN |
| | ACCORDANCE WITH FBC-R SECTION N1100.0.1. |
| | |
| | 6. ACCORDING TO PAGE 2.0, TWO WINDOWS ON THE EXISTING |
| | HOUSE ARE BEING ELIMINATED. THIS CONSTITUTES A LEVEL 2 |
| | ALTERATION (AS DECLARED ON PLANS). ALL RECONFIGURED |
| | SPACES INTENDED FOR OCCUPANCY IN ANY WORK AREA SHALL BE |
| | PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR |
| | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL PER FBC-EB 709.1. SHOW THE EXISTING HOUSE |
| | WITHOUT THESE WINDOWS WILL MEET THE VENTILATION |
| | REQUIREMENTS OF FBC-M SECTION 402 OR 403. |
| | |
| | 7. PLEASE SEE PLUMBING COMMENTS REGARDING SIGNATURE, |
| | SEAL AND TITLE BLOCK OF THE DESIGN PROFESSIONAL. |
| | |