| 2009-06-08 16:15:20 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. NOTE: THIS MAY BE RECORDED AT TIME OF |
| | PERMIT PICK UP. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. REVISE VALUATION TO INCLUDE ALL MATERIALS, LABOR |
| | AND ALL PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.0.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- TAKE PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 5- SHEET 1.0 NEEDS TO BE SIGNED AND SEALED BY THE |
| | ENGINEER AS REQUIRED BY SEC. 471 FLORIDA STATUTE. |
| | |
| | 6- SHEET 2.0: |
| | A) UPDATE GENERAL DEMOLITION NOTE #1. REFER TO 2009 |
| | REVISIONS, NOT 2007. |
| | |
| | B) SPECIFY SIZE AND TYPE OF EXISTING BEDROOM WINDOWS |
| | THAT ARE GOING TO BE REMOVED. AND SIZE AND TYPE OF |
| | BEDROOM WINDOWS TO REMAIN TO VERIFY COMPLIANCE WITH THE |
| | EGRESS REQUIREMENTS OF SEC. 601.2 OF 2007 FLORIDA |
| | EXISTING BUILDING CODE. |
| | |
| | 7- SHEET 3.0: REVISE THICKNESS OF STUCCO SHOWN ON WALL |
| | LEGEND. NEED 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE |
| | R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- SHEET 3.1: |
| | A) REVISE STUCCO THICKNESS ON DETAILS LEGEND #5. |
| | REQUIRES 7/8" STUCCO, NOT 3/4". TABLE R702.1(1). |
| | |
| | B) CLARIFY WHY THE WINDOW/DOOR SCHEDULE CALLS FOR MAX. |
| | AND MIN. WIND PRESSURES INSTEAD OF POSITIVE AND |
| | NEGATIVE PRESSURES. |
| | |
| | 9- SHEET 6.2: SPECIFY HOW LONG ARE THE 1/2" ANCHOR |
| | BOLTS SPECIFIED ON DETAILS 1 AND 2 TO HOLD THE 2X6 |
| | BOTTOM PLATE. SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 10- PROVIDE ENGINEERING ANALYSIS SHOWING WHY THE 2X6 |
| | WOOD LEDGER THAT IS RECEIVING ENTIRE ROOF IS ONLY |
| | ATTACHED TO THE WALL SHEATHING AND NOT TO THE STUDS. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | |
| | 11- SHEET 7.1: |
| | A) DETAIL 1: REVISE STUCCO THICKNESS TO COMPLY WITH |
| | TABLE R702.1(1). ALSO, COORDINATE LEDGER ATTACHMENT |
| | WITH ITEM #10 ABOVE. |
| | |
| | B) DETAIL 2: COORDINATE LEDGER ATTACHMENT WITH ITEM #10 |
| | |
| | 12- SHEET 7.2: REVISE NOTE BELOW WIND LOAD SCHEDULE. |
| | REFER TO 2007 FBC WITH 2009 REVISIONS, NOT 2004. |
| | |
| | 13- SHEET 8: |
| | A) NEED TO PROVIDE CONTINUOUS VENTILATION AS REQUIRED |
| | BY SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE STUCCO THICKNESS. SEE ITEM #8 ABOVE. |
| | |
| | C) LEDGER ATTACHMENT TO EXISTING WALL. COORDINATE WITH |
| | ITEM #10 ABOVE. |
| | |
| | D) CLARIFY SIZE OF ANCHOR HOLDING THE BOTTOM PLATE. |
| | 1/2" OR 5/8". COORDINATE WITH DETAILS ON SHEET 6.2. |
| | ALSO, SPECIFY HOW LONG ARE THEY REQUIRED TO BE. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL FOR ALL SIMPSON STRUCTURAL |
| | CONNECTORS SPECIFIED ON PLANS AND DETAILS AS REQUIRED |
| | BY DCA RULE 9B-72. PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE CONNECTOR. |
| | |
| | 15- ENGINEER OF RECORD TO REVIEW AND APPROVE (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS. RUBBER |
| | STAMP SAYING THAT THIS PRODUCT APPROVAL HAS BEEN |
| | REVIEWED DOESN'T IDENTIFY THE ENGINEER WHO REVIEWED. IN |
| | ADDITION ALL FLORIDA PRODUCT APPROVAL SUBMITTED WERE |
| | REMOVED FROM THE SUBMITTED PACKAGE BECAUSE THEY |
| | CORRESPOND TO 2004 CODE AND CODE IN EFFECT IS 2007. YOU |
| | MAY USE NOA ALONE. |
| | |
| | 16- FLAT ROOF PRODUCT APPROVAL NOA 07-1219.09 SUBMITTED |
| | REQUIRES RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS. SUCH CALCULATIONS NEED TO |
| | BE SIGNED AND SEALED AS REQUIRED BY GENERAL LIMITATION |
| | #7 ON SHEET 19 OF NOA SUBMITTED. PROVIDE SIGNED AND |
| | SEALED CALCULATIONS. |
| | |