| 2009-05-22 16:24:23 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON SHEET 20 | | | OF 20 OF NOA 08-0512.06 SUBMITTED. ASSEMBLY SELECTED ON | | | SHEET 19 OF 20 IS GOOD FOR A MAXIMUM DESIGN PRESSURE OF | | | -52.5PSF. NEED TO PROVIDE NAIL ENHANCING FOR PERIMETER | | | AND CORNER AREAS IN ORDER TO MEET THE DESIGN PRESSURES | | | REQUIREMENTS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS | | | NEEDS TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE | | | 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE, | | | THIS BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC. R301 | | | OF 2009 REVISIONS FOR REVISIONS DONE TO THE EXPOSURE | | | CATEGORY. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. 108.3 | | | CITY AMENDMENTS TO FBC. OWES $78.17 FOR UPDATED | | | VALUATION. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|