| 2009-05-26 13:00:58 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | ONLY ONE COPY PROVIDED (TWO REQUIRED) AND ONE COLUMN | | | WAS LEFT BLANK. THE "SHUTTER CONNECTION MOUNTING TYPE" | | | SHOULD CORRELATE WITH THE ANCHOR CHARTS; IN THIS CASE, | | | THEY ARE NAMED SECTION 1 THROUGH SECTION 13, TOP AND | | | BOTTOM, FOR CONCRETE AND BLOCK (SEE SHEET 10). IT | | | APPEARS THAT YOU MAY BE PROPOSING TO USE SECTION 7 | | | (BOTH TOP AND BOTTOM). | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9B72, WWW.FLORIDABUILDING.ORG. PLEASE PRINT COVER | | | SHEET FROM THE WEBSITE. | | | | | | 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. | | | | | | 4. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE, ITEM 1 ABOVE. FBC R301, FBC1609, | | | FBC*106. | | | | | | 5. SEE FBC R 301 OR FBC1609, ASCE7-05, THIS JOB IS IN | | | EXPOSURE C. PLEASE REVISE DESIGN PRESSURES ACCORDINGLY. | | | | | | | | | |
|