Plan Review Notes
Plan Review Notes For Permit 09050471
Permit Number 09050471
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-26 13:00:58****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 ONLY ONE COPY PROVIDED (TWO REQUIRED) AND ONE COLUMN
 WAS LEFT BLANK. THE "SHUTTER CONNECTION MOUNTING TYPE"
 SHOULD CORRELATE WITH THE ANCHOR CHARTS; IN THIS CASE,
 THEY ARE NAMED SECTION 1 THROUGH SECTION 13, TOP AND
 BOTTOM, FOR CONCRETE AND BLOCK (SEE SHEET 10). IT
 APPEARS THAT YOU MAY BE PROPOSING TO USE SECTION 7
 (BOTH TOP AND BOTTOM).
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG. PLEASE PRINT COVER
 SHEET FROM THE WEBSITE.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 4. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 1 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 5. SEE FBC R 301 OR FBC1609, ASCE7-05, THIS JOB IS IN
 EXPOSURE C. PLEASE REVISE DESIGN PRESSURES ACCORDINGLY.
  
  
  