2009-06-01 13:51:41DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 FBC-2007 CHAPTER 1
  
 1. SHT D-1 CODE REFERENCES TO READ FBC-2007 WITH 2009
 SUPPLEMENTS. SECTION 106.1.1.
  
 2. SHT D-1 IN THE REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. ALL REMOVAL OF
 PIPING SHALL BE WITH 2 FEET OF AN ACTIVE BRANCH LINE OR
 BUILDING DRAIN LINE. SECTION 704.5. SOME LINES APPEAR
 TO BE MORE THAN 2 FEET. (SEE RISER DIAGRAM ON SHEET 3
 OF 3).
  
 3. THE FOLLOWING INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE:
 ___FOR W.C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.