Plan Review Notes
Plan Review Notes For Permit 09050468
Permit Number 09050468
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-12 16:20:34**PROVISO**
  
 RETURN AIR TRANSFER DUCT IN EXAM ROOM SHALL BE MIN. 9"
 ROUND TO MEET EXCEPTION UNDER FBC-M 601.4 FOR BALANCED
 RETURN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: