| 2009-06-01 08:36:49 | *** DENIED REVIEW **** |
| | |
| | |
| | 1) NOTE: PLEASE ADJUST AND CORRECT SOME OF THE |
| | FOLLOWING CODES ON PLANS. |
| | PLANS NEED TO STATE THE FOLLOWING. |
| | 2007 FBC W/ 2009 GLITCH AMENDMENTS. ( PLANS STATE 2007 |
| | AND 2008/ GLITCH AMENDMENTS ) |
| | |
| | 2002 NFPA-72. (PLANS STATE 2006) |
| | |
| | 2006 NFPA-1 (PLANS STATE 2007 FIRE PREVENTION CODE. |
| | NFPA-1 IS THE FIRE PREVENTION CODE) |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.5 |
| | |
| | 3) NOTE: PLEASE IDENTIFY ALL CIRCUITS SPECIFIC TO ROOMS |
| | AND AREAS IN WHICH THEY FEED. THESE MAY BE ALPHA OR |
| | NUMERIC DESIGNATIONS. PLANS STATE THE WORDING OF |
| | *NOTES* ON MANY OF THE SPACES. WHAT NOTES ARE THESE AS |
| | SOME OF THE NOTES ON THE PLANS DO NOT SEEM TO |
| | COORDINATE WITH THE PANELS WITH WHAT THEY WOULD BE? |
| | PLEASE SEE NEC HANDBOOK COMMENTARY UNDER 408..4 AS ALL |
| | CIRCUITS NEED TO BE SPECIFIC. |
| | |
| | 4) NOTE: PLEASE COORDINATE PANEL AND SERVICE |
| | CALCULATIONS. PANEL IS NOTED AS BEING A 150AMP PANEL, |
| | HOWEVER THE CALCULATIONS NOTE THE EXISTING PANEL IS |
| | 200AMP. |
| | 240,408, ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | |
| | |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |