Plan Review Notes
Plan Review Notes For Permit 09050463
Permit Number 09050463
Review Stop P
Sequence Number 1
Notes
Date Text
2009-05-27 14:36:17DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1 (ADMIN)
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT IR-1. MORE INFORMATION REQUIRED. PLEASE INDICATE
 THE LOCATION OF THE WATER SOURCE, THE BACKFLOW
 PREVENTOR IF WATER SOURCE IS POTABLE WATER, THE
 CONTROLLER AND THE RAIN SENSOR. SECTIONS 106.1.1, 608 &
 APPENDIX F & FS 373.62.
  
 2. THE SEAL DOES NOT IMPRESS ALL THE INFORMATION
 REQUIRED BY FAC 61G10-11.010. PLEASE MAKE SURE ALL
 INFORMATION REQUIRED BY FLORIDA STATUTES IS LEGIBLE
 WHEN SEALING THE PLANS. FS 481.321.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  