| Plan Review Notes For Permit 09050443 |
| Permit Number |
09050443 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-21 12:04:54 | RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- SELECTED ASSEMBLY ON PAGE 32 OF NOA 08-0227.09 | | | SUBMITTED IS LIMITED BY GENERAL LIMITATION #9. THIS | | | LIMITATION DOESN'T ALLOW FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS. THE MAXIMUM DESIGN PRESSURE | | | ON SELECTED ASSEMBLY IS -45PSF AND IT CAN'T BE | | | INCREASED. DESIGN PRESSUES FOR THIS BUILDING IN THIS | | | AREA ARE HIGHER THAN 45PSF. SEE GENERAL LIMITATION #9 | | | ON SHEET 39. NEED TO SELECT ASSEMBLY THAT IS LIMITED BY | | | GENERAL LIMITATION #7 THAT DOES ALLOW FOR NAIL | | | ENHANCING BY RUNNING RAS 117 CALCULATIONS. SEE GENERAL | | | LIMITATION #7. | | | | | | 2- ACCORDING TO NOA SUBMITTED GENERAL LIMITATION #7 | | | REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS. | | | PROVIDE SIGNED AND SEALED CALCULATIONS. | | | ***NOTE: DESIGN PROFESSIONAL WHEN RUNNING THE | | | CALCULATIONS NEEDS TO TAKE INTO CONSIDERATION THAT | | | ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA | | | RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE | | | C. SEE 2009 REVISIONS SEC. R301. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|