| Date |
Text |
| 2009-06-01 14:22:57 | ** DENIED 2ND REVIEW** |
| | |
| | ** FIRST REVIEW WITH NEW PLANS. |
| | |
| | SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING. THERE ARE ALSO SOME NEW ITEMS BASED ON |
| | CHANGES MADE TO PLANS WHICH HAVE CREATED NEW COMMENTS |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS AT A MINIMUM. |
| | 2005 NFPA-70 |
| | PLANS MAY NOT STATE LATEST EDITION AS THE STATE WILL BE |
| | ADOPTING NEW CODES. |
| | PER FS 553.73 AND ADOPTED 2007 FBC W2009 REVISIONS THE |
| | ADOPTED VERSION SHALL BE PART OF THE DESIGN DOCUMENTS. |
| | |
| | 2) NOTE: PREVIOUS COMMENT WITH RESPECT TO THE VALUE FOR |
| | THE APPLIED SCOPE OF WORK. ALL LABOR, MATERIALS, |
| | EQUIPMENT SHALL BE INCLUDED EVEN IF ANY OF THESE ITEMS |
| | ARE OWNER SUPPLIED. |
| | THE VALUE WAS ADJUSTED TO $5K HOWEVER THIS VALUE IS |
| | STILL LOW. THE VALUE HAS BEEN ADJUSTED BY THIS OFFICE |
| | USING THE ADOPTED GUIDES IN MARSHALLS AND SWIFT PER FBC |
| | 108.3. |
| | THE VALUE ADJUSTED WAS NOT FOR LINEAR FT OF CONDUITS |
| | AND WIRING AND NO SITE PLANS WAS SUBMITTED. |
| | THERE WILL BE FEES DUE. THE NEW APPLIED VALUE WAS |
| | ADJUSTED TO $32K. A BALANCE OF $654.48 WILL BE DUE |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | 3) NOTE: PLEASE COORDINATE RISERS AND EQUIPMENT RISER. |
| | RISER INDICATES A NEW 30KVA TRANSFORMER HOWEVER THE |
| | EQUIPMENT RISER INDICATES 37 KVA. THIS WILL AFFECT THE |
| | OVER CURRENT PROTECTION. PLEASE BE SURE TO COORDINATE. |
| | PLEASE BE SURE TO SEE 450.3 FOR MAXIMUM OCP DEPENDING |
| | ON CHANGES. |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS. |
| | |
| | 4) NOTE: PLEASE INCLUDE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. 110.9 |
| | ALL MAINS, PANELS, BREAKERS ETC SHALL BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT. |
| | |
| | 5) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE SYSTEM |
| | FOR THE SEPARATELY DERIVED TRANSFORMERS PER |
| | 250.20,250.30,250.50, 250.56 AND 250.66 FOR SIZING OF |
| | GROUNDING ELECTRODES. |
| | |
| | 6) NOTE: PLEASE CHECK THE SIZE OF THE CONDUCTORS FROM |
| | SERVICE MAIN TO GUTTER. PLEASE SEE 310.15(B)(2)(A) FOR |
| | MORE THAN THREE CURRENT CARRYING CONDUCTORS INSIDE THE |
| | CONDUIT. PLEASE ALSO SEE TEMPERATURE DE-RATINGS FOR |
| | AMBIENT AIR. BASED ON 310.16 EVEN STARTING AT THE 90 |
| | DEGREE COLUMN WITH THE DE-RATING THE AMPACITY OF THE |
| | CONDUCTORS FALL BELOW 200AMPS. AS THE RISER DOES NOT |
| | INCLUDE ALL LOADS THERE ARE SOME MINIMUM CODE CONCERNS |
| | ON SIZING. |
| | PLEASE BE SURE TO SEE 110.14 FOR CONNECTION RATINGS. |
| | |
| | *** ALMOST ALL CONDUCTORS ON RISER ARE SHOWN AS COPPER |
| | WITH THE EXCEPTION OF THE CONDUCTORS TO THE 37KVA AND |
| | THE FEEDERS FROM MAIN TO GUTTER. PLEASE VERIFY. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |