Plan Review Notes
Plan Review Notes For Permit 09050431
Permit Number 09050431
Review Stop E
Sequence Number 2
Notes
Date Text
2009-06-01 14:22:57** DENIED 2ND REVIEW**
  
 ** FIRST REVIEW WITH NEW PLANS.
  
 SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING. THERE ARE ALSO SOME NEW ITEMS BASED ON
 CHANGES MADE TO PLANS WHICH HAVE CREATED NEW COMMENTS
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70
 PLANS MAY NOT STATE LATEST EDITION AS THE STATE WILL BE
 ADOPTING NEW CODES.
 PER FS 553.73 AND ADOPTED 2007 FBC W2009 REVISIONS THE
 ADOPTED VERSION SHALL BE PART OF THE DESIGN DOCUMENTS.
  
 2) NOTE: PREVIOUS COMMENT WITH RESPECT TO THE VALUE FOR
 THE APPLIED SCOPE OF WORK. ALL LABOR, MATERIALS,
 EQUIPMENT SHALL BE INCLUDED EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED.
 THE VALUE WAS ADJUSTED TO $5K HOWEVER THIS VALUE IS
 STILL LOW. THE VALUE HAS BEEN ADJUSTED BY THIS OFFICE
 USING THE ADOPTED GUIDES IN MARSHALLS AND SWIFT PER FBC
 108.3.
 THE VALUE ADJUSTED WAS NOT FOR LINEAR FT OF CONDUITS
 AND WIRING AND NO SITE PLANS WAS SUBMITTED.
 THERE WILL BE FEES DUE. THE NEW APPLIED VALUE WAS
 ADJUSTED TO $32K. A BALANCE OF $654.48 WILL BE DUE
 BEFORE PERMIT ISSUANCE.
  
 3) NOTE: PLEASE COORDINATE RISERS AND EQUIPMENT RISER.
 RISER INDICATES A NEW 30KVA TRANSFORMER HOWEVER THE
 EQUIPMENT RISER INDICATES 37 KVA. THIS WILL AFFECT THE
 OVER CURRENT PROTECTION. PLEASE BE SURE TO COORDINATE.
 PLEASE BE SURE TO SEE 450.3 FOR MAXIMUM OCP DEPENDING
 ON CHANGES.
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 4) NOTE: PLEASE INCLUDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. 110.9
 ALL MAINS, PANELS, BREAKERS ETC SHALL BE RATED FOR THE
 AVAILABLE FAULT CURRENT.
  
 5) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE SYSTEM
 FOR THE SEPARATELY DERIVED TRANSFORMERS PER
 250.20,250.30,250.50, 250.56 AND 250.66 FOR SIZING OF
 GROUNDING ELECTRODES.
  
 6) NOTE: PLEASE CHECK THE SIZE OF THE CONDUCTORS FROM
 SERVICE MAIN TO GUTTER. PLEASE SEE 310.15(B)(2)(A) FOR
 MORE THAN THREE CURRENT CARRYING CONDUCTORS INSIDE THE
 CONDUIT. PLEASE ALSO SEE TEMPERATURE DE-RATINGS FOR
 AMBIENT AIR. BASED ON 310.16 EVEN STARTING AT THE 90
 DEGREE COLUMN WITH THE DE-RATING THE AMPACITY OF THE
 CONDUCTORS FALL BELOW 200AMPS. AS THE RISER DOES NOT
 INCLUDE ALL LOADS THERE ARE SOME MINIMUM CODE CONCERNS
 ON SIZING.
 PLEASE BE SURE TO SEE 110.14 FOR CONNECTION RATINGS.
  
 *** ALMOST ALL CONDUCTORS ON RISER ARE SHOWN AS COPPER
 WITH THE EXCEPTION OF THE CONDUCTORS TO THE 37KVA AND
 THE FEEDERS FROM MAIN TO GUTTER. PLEASE VERIFY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved