| 2009-05-21 16:11:57 | **DENIED ** |
| | |
| | 1) NOTE: THE VALUE FOR COMPLETED SCOPE OF WORK |
| | INCLUDING ALL LABOR, MATERIALS, EQUIPMENT AND DESIGN |
| | FEES NEEDS TO BE INCLUDING EVEN IF ANY OF THESE ITEMS |
| | ARE OWNER SUPPLIED. FBC 108.3 |
| | THE ELECTRICAL EQUIPMENT ALONE CAN NOT BE PURCHASED FOR |
| | THE APPLIED VALUE STATED. |
| | |
| | 2) NOTE: PLANS SHALL BE COMPLETED BY AN PROFESSIONAL |
| | ENGINEER PER FS 471.003 |
| | PLEASE BE SURE THE INFORMATION IS COMPLETE ON PLANS AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: PLEASE BE SURE RISER IS COMPLETE WITH ALL |
| | INFORMATION FOR CONDUCTORS, CONDUITS, PANELS, |
| | EQUIPMENT, MAINS, GROUNDING ETC. |
| | THERE ARE SEVERAL ITEMS MISSING. |
| | NO INDICATION OF TAP CONDUCTORS ON THE SECONDARY SIDE |
| | OF THE TRANSFORMER TERMINATING IN OCP PER 24.21, |
| | 240.4,310.16. |
| | NO PANEL SCHEDULES. 408.4 |
| | NO LOADS INDICATED. 220 |
| | NO MINIMUM SIZE OF GROUNDING ELECTRODES OR GROUNDING |
| | ELECTRODE CONDUCTORS. 250.50,250.66,250.52(5). |
| | |
| | ** THESE ARE SOME EXAMPLES GIVEN AS A BENEFIT. NEW |
| | ENGINEERED PLANS WILL BE REVIEWED. |
| | |
| | 4) NOTE: PLEASE BE SURE TO CORRECT ADDRESS ON PERMIT |
| | APPLICATION WHEN RE-SUBMITTING TO 4335 EASLEY DR. |
| | FAC61G15-23.002 |
| | |
| | 5) NOTE: THE OWNER INFORMATION OF PROPERTY LISTED ON |
| | PERMITTED APPLICATION IS INCORRECT. PLEASE UPDATE. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |