| 2009-06-16 11:00:19 | 2007 FBC | | | INSTALL GENERATOR | | | | | | DENIED BY MECHANICAL | | | | | | 1) SHOW COMPLIANCE WITH NFPA 37-4.1.4 WHICH REQUIRES | | | GENERATORS TO BE LOCATED AT LEAST 5 FEET FROM OPENINGS | | | AND AT LEAST 5 FEET FROM STRUCTURES HAVING COMBUSTIBLE | | | WALLS. THE AERIAL PHOTO FOR THIS PROPERTY APPEARS TO | | | SHOW A STRUCTURE WHERE THE PATIO IS LOCATED ON THE | | | SURVEY. M 915.2 NOTE: IF MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS REQUIRE GREATER CLEARANCES, THEY SHALL BE | | | FOLLOWED. FBC R M1306.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|