2009-06-16 11:00:192007 FBC
 INSTALL GENERATOR
  
 DENIED BY MECHANICAL
  
 1) SHOW COMPLIANCE WITH NFPA 37-4.1.4 WHICH REQUIRES
 GENERATORS TO BE LOCATED AT LEAST 5 FEET FROM OPENINGS
 AND AT LEAST 5 FEET FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. THE AERIAL PHOTO FOR THIS PROPERTY APPEARS TO
 SHOW A STRUCTURE WHERE THE PATIO IS LOCATED ON THE
 SURVEY. M 915.2 NOTE: IF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS REQUIRE GREATER CLEARANCES, THEY SHALL BE
 FOLLOWED. FBC R M1306.1
  