2009-06-16 11:18:182007 FBC
 INSTALL NATURAL GAS GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY THE NUMBER, TYPE, SIZE AND LOCATIONS OF THE
 FASTENERS THAT WILL BE USED TO ANCHOR THE GENERATOR TO
 THE 5" THICK CONCRETE PAD IN ORDER TO RESIST SLIDING,
 OVERTURNING AND UPLIFT FOR 140 MPH WIND LOAD. FBC
 1604.9
  
 2) THE VALUE FOR THE WORK IS LOW. THE VALUE FOR THE
 GENERATOR ALONE IS OVER $12,000.00, NOT INCLUDING THE
 TRANSFER SWITCH, WIRE, GAS PIPING AND LABOR. PLEASE
 REVISE.
 FBC 108.1* CITY AMENDMENTS.
  