| Plan Review Notes For Permit 09050419 |
| Permit Number |
09050419 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-05-27 08:50:29 | RESIDENTIAL (R3) RE-ROOFING BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON NOA 08-0827.18 | | | SUBMITTED. HIGHLIGHTED ASSEMBLY HAS A MAXIMUM DESIGN | | | PRESSURE OF -60PSF. THIS BUILDING IS LOCATED ON A | | | 140MPH WIND ZONE AREA AND THE DESIGN PRESSURES AT | | | PERIMETER AND CORNER AREAS ARE HIGHER THAN -60PSF. | | | THAT'S WHY NAIL ENHANCING IS REQUIRED. | | | ***NOTE: DESIGN PROFESSIONAL PERFORMING THE | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE | | | THIS BUILDING IS LOCATED ON EXPOSURE C, NOT B. SEE | | | REVISIONS TO THE EXPOSURE CATEGORY ON SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 2- NOA SUBMITTED IS INCOMPLETE. PROVIDE ALSO THE FIRST | | | PAGES OF NOA THAT CONTAINS ALL APPROVED COMPONENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|