2009-05-27 08:50:29RESIDENTIAL (R3) RE-ROOFING BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON NOA 08-0827.18
 SUBMITTED. HIGHLIGHTED ASSEMBLY HAS A MAXIMUM DESIGN
 PRESSURE OF -60PSF. THIS BUILDING IS LOCATED ON A
 140MPH WIND ZONE AREA AND THE DESIGN PRESSURES AT
 PERIMETER AND CORNER AREAS ARE HIGHER THAN -60PSF.
 THAT'S WHY NAIL ENHANCING IS REQUIRED.
 ***NOTE: DESIGN PROFESSIONAL PERFORMING THE
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE
 THIS BUILDING IS LOCATED ON EXPOSURE C, NOT B. SEE
 REVISIONS TO THE EXPOSURE CATEGORY ON SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- NOA SUBMITTED IS INCOMPLETE. PROVIDE ALSO THE FIRST
 PAGES OF NOA THAT CONTAINS ALL APPROVED COMPONENTS.
  