1 |
|
| Notes |
| Date |
Text |
| 2009-05-20 11:50:29 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON NOA 07-1203.01 | | | SUBMITTED. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THE EXPOSURE CATEGORY AS | | | REQUIRED BY 2009 REVISIONS TO SEC. R301.2.1.4.3 OF 2004 | | | FLORIDA RESIDENTIAL CODE. WHAT USED TO BE CONSIDERED | | | EXPOSURE B, NOW MAY BE CONSIDERED EXPOSURE C. SEE 2009 | | | REVISIONS. | | | | | | 2- CLEARLY IDENTIFY ON PRODUCT APPROVAL SUBMITTED WHICH | | | APPROVED ASSEMBLY AND FASTENING OPTION IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES AND NAIL ENHANCING REQUIREMENTS OF GENERAL | | | LIMITATION #7. | | | | | | 3- CLARIFY IF RE-ROOFING ENTIRE ROOF OR ONLY A SMALL | | | PART OF THE ROOF. PERMIT APPLICATION CALLS FOR ONLY | | | 141SF OF ROOF TO BE REPLACED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | (561)805-6712 |
|