Plan Review Notes
Plan Review Notes For Permit 09050415
Permit Number 09050415
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-28 15:47:302007 FBC
 ADDITION
  
 DENIED BY BUILDING
  
 1) THE FOUNDATION PLAN ON SHEET 5.0 SPECIFIES A 4"
 CONCRETE SLAB. THE ELEVATION AND SECTIONS SHOW A 6"
 SLAB. PLEASE CORRECT.
  
 2) THE DETAIL TAG FOR (1 ON 8.0) ON SHEET 5.0 LISTS THE
 WRONG SHEET. IT SHOULD BE 1 ON 7.0. PLEASE CORRECT.
  
 3) ON SHEET 6.0 THE FRAMING NOTES SPECIFY 19/32" (5/8")
 PLYWOOD FOR ROOF SHEATHING AND THE NOTE ON THE DRAWINGS
 ON 6.0 AND 7.0 SPECIFIES 3/4" PLYWOOD. PLEASE CORRECT.
  
 4) THE WINDLOAD PRESSURES SPECIFIED FOR THE EXTERIOR
 DOOR TO THE LAUNDRY ROOM ON SHEET 3.1 ARE TOO LOW FOR
 AN ENCLOSED STRUCTURE LOCATED IN EXPOSURE CATEGORY C
 AND AN IMPORTANCE FACTOR OF 1.00. FBC R TABLE R301.2.1
  
 5) THE WINDLOAD SCHEDULE FOR THE OPEN ATTACHED PATIO IS
 INCORRECT. THE PATIO AND LAUNDRY ROOM ARE ATTACHED TO
 THE DWELLING AND ARE NOT STRUCTURALLY INDEPENDENT. THE
 SINGLE FAMILY DWELLING IS A CATEGORY II OCCUPANCY, AS
 WELL AS, THE ATTACHED COVERED PATIO AND LAUNDRY ROOM.
 THEREFORE, THE IMPORTANCE FACTOR IS 1.00 AND NOT 0.77.
 PLEASE CORRECT AND REVISE THE ROOF WINDLOADS. FBC
 R301.2.1
  
 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE FOR THE
 EXTERIOR DOORS TO THE LAUNDRY ROOM AS REQUIRED BY FAC
 RULE 9B-72.
  
 7) THE DOOR SCHEDULE ON SHEET 3.1 INDICATES STORM
 PANELS FOR THE EXTERIOR DOORS TO THE LAUNDRY ROOM.
 STORM PANELS ONLY PROVIDE IMPACT PROTECTION FOR GLAZED
 AREAS. THEY ARE DO NOT PREVENT WIND PRESSURES FROM
 AFFECTING THE BUILDING ENVELOPE. THAT IS PROVIDED BY
 THE WINDOW OR DOOR THAT IS INSTALLED IN THE EXTERIOR
 OPENING. R301.2.1.2
  
 8) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE AND KEY
 PLAN SPECIFYING THE OPENINGS THAT WILL BE SHUTTERED.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE AND SPACING,
 SPAN, ETC.
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STORM PANELS ARE MISSING SOME OF THE PAGES. SUBMIT 2
 COMPLETE COPIES OF THE PRODUCT APPROVALS.
  
 10) THE SYSTEM SELECTED FROM THE MODIFIED ROOF COVERING
 PRODUCT APPROVALS HAS A MAXIMUM DESIGN PRESSURE OF -52
 PSF, WHICH WILL REQUIRE ENHANCED FASTENING AT THE
 CORNER AND PERIMETER AREAS FOR EXPOSURE C AND 140 MPH
 WINDSPEED. SUBMIT 2 SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION #7 OF THE NOA.
  
 11) THE VALUATION THAT IS INDICATED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON
 THE PLANS. THE VALUE HAS BEEN INCREASED TO $17,111.00
 BASED ON ICC VALUATION DATA. ADDITIONAL PERMIT AND
 RADON FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]