| Plan Review Notes For Permit 09050398 |
| Permit Number |
09050398 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-21 16:28:05 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- REVISE INSTALLATION SCHEDULE ANCHOR SPACING FOR | | | OPENINGS 1 AND 2 TO MATCH THE CALCULATED DESIGN | | | PRESSURES. CALCULATED DESIGN PRESSURES ARE -57.2. | | | THEREFORE ANCHOR SPACING FOR -57 CAN'T BE USED. NEED TO | | | USE HIGHER DESIGN PRESSURES ANCHOR SPACING. | | | | | | 2- CLARIFY IF SUBSTRATE TO RECEIVE SHUTTERS IS POURED | | | CONCRETE ON TOP AND BOTTOM. TYPICALLY THERE IS A | | | PRECAST CONCRETE LINTEL OR POURED CONCRETE BEAM ON TOP, | | | BUT WINDOW SILL MAY NOT BE POURED CONCRETE. PROVIDE | | | PROOF THAT WINDOW SILL HAS MIN. 3,320 PSI CONCRETE | | | STRENGTH AS REQUIRED BY THE PRODUCT APPROVAL OR USE THE | | | CONCRETE BLOCK ANCHOR SPACING TO VERIFY COMPLIANCE WITH | | | THE PRODUCT APPROVAL AND CALCULATED DESIGN PRESSURES | | | REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | REVISE ANCHOR SPACING AS REQUIRED. | | | | | | 3- REVISE LENGTH OF TAPCON. 1-3/4" TAPCON DOESN'T | | | PROVIDE THE MIN. REQUIRED EMBEDMENT OF 1-3/4" ON | | | CONCRETE INSTALLATIONS. | | | NOTE: MINIMUM EMBEDMENT EXCLUDES STUCCO OR ANY OTHER | | | FINISH. ALSO, MINIMUM EMBEDMENT REQUIRED FOR CONCRETE | | | BLOCK INSTALLATION IS 1-1/4" EXCLUDING STUCCO ALSO. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|