2009-07-28 13:39:51PLANS HAVE BEEN HELD AT MY DESK AFTER MULTIPLE ATTEMPTS
 TO GET CORRECTED ENERGY CALCULATIONS FROM THE DESIGN
 TEAM BY EMAIL OR DELIVERED IN PERSON. PLANS ARE NOW
 DENIED AND WILL NEED TO BE RESUBMITTED WITH CORRECTED
 ENERGY CALCULATIONS. OUTSTANDING ISSUES ON THE ENERGY
 CALCULATIONS ARE AS FOLLOWS:
  
 1. CALCULATIONS CALL FOR "FACTORY SEALED AIR HANDLER
 CREDIT." THE AIR HANDLER IS EXISTING AND NO SUCH CREDIT
 IS AVAILABLE. REVISE CALCULATIONS REMOVING THIS CREDIT.
  
 2. LINE 15 CALLS FOR A WHOLE HOUSE FAN CREDIT. THIS
 HOUSE MUST DEMONSTRATE THAT THE CRITERIA STATED IN
 FBC-R SECTION N1107.A.6 HAVE BEEN MET TO TAKE THIS
 CREDIT. PROVIDE SUCH DOCUMENTATION OR REMOVE THIS
 CREDIT FROM THE CALCULATIONS AND RESUBMIT.
  