| Plan Review Notes For Permit 09050383 |
| Permit Number |
09050383 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-28 13:39:51 | PLANS HAVE BEEN HELD AT MY DESK AFTER MULTIPLE ATTEMPTS | | | TO GET CORRECTED ENERGY CALCULATIONS FROM THE DESIGN | | | TEAM BY EMAIL OR DELIVERED IN PERSON. PLANS ARE NOW | | | DENIED AND WILL NEED TO BE RESUBMITTED WITH CORRECTED | | | ENERGY CALCULATIONS. OUTSTANDING ISSUES ON THE ENERGY | | | CALCULATIONS ARE AS FOLLOWS: | | | | | | 1. CALCULATIONS CALL FOR "FACTORY SEALED AIR HANDLER | | | CREDIT." THE AIR HANDLER IS EXISTING AND NO SUCH CREDIT | | | IS AVAILABLE. REVISE CALCULATIONS REMOVING THIS CREDIT. | | | | | | 2. LINE 15 CALLS FOR A WHOLE HOUSE FAN CREDIT. THIS | | | HOUSE MUST DEMONSTRATE THAT THE CRITERIA STATED IN | | | FBC-R SECTION N1107.A.6 HAVE BEEN MET TO TAKE THIS | | | CREDIT. PROVIDE SUCH DOCUMENTATION OR REMOVE THIS | | | CREDIT FROM THE CALCULATIONS AND RESUBMIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|