| 2009-05-22 14:35:22 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH S.W. ENGINEERING INC. TITLE BLOCKS |
| | SHALL INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | IN THE TITLE BLOCK PER FAC 61G15-23.002(2) & FS |
| | 471.025. -- ALSO THE ADDRESS IN THE TITLE BLOCK DOES |
| | NOT REFLECT THE ADDRESS OF RECORD ON THE STATE OF |
| | FLORIDA DEPT OF BUSINESS & PROFESSIONAL REGULATION, |
| | (DBPR), WEBSITE. PLEASE UPDATE THE TITLE BLOCKS OR THE |
| | DBPR WEBSITE PRIOR TO RESUBMITTING PLANS TO THE CITY |
| | WPB FOR REVIEW. (SEE ATTACHED SHEET). |
| | |
| | 2. SHT 8.0 MANY REFERENCES TO FBC-2004 EDITION IN THE |
| | PLUMBING NOTES. ALL APPLICATIONS FOR PERMIT ON OR AFTER |
| | MARCH 1, 2009 SHALL BE DESIGNED TO THE FBC-2007 |
| | EDITION. PLEASE UPDATE THE DESIGN REFERENCES TO THE |
| | CURRENT CODE CYCLE. |
| | |
| | 3. SHT 8.0 THE WATER CLOSET IS NOT VENTED AS INDICATED. |
| | SECTION P3101.2.1. (SEE RED LINE EXAMPLE OF PIPING FOR |
| | W/C). |
| | |
| | 4. SHT 8.0 CLEANOUTS ARE REQUIRED NEAR THE JUNCTION OF |
| | THE BUILDING DRAIN AND THE BUILDING SEWER. SECTION |
| | P3005.2.7. THE W/C DRAIN LINE AND THE LAVS/SHOWER DRAIN |
| | LINES REQUIRE CLEANOUTS AS THEY EXIT THE BUILDING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |