Plan Review Notes
Plan Review Notes For Permit 09050383
Permit Number 09050383
Review Stop M
Sequence Number 1
Notes
Date Text
2009-06-04 09:15:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. UPDATE CODE REFERENCE ON PAGE 9.0. THE CURRENT CODE
 IN EFFECT AS OF MARCH 1, 2009 IS THE 2007 FLORIDA
 BUILDING CODE W/ 2009 SUPPLEMENT.
  
 2. THE PROPOSED SCOPE OF WORK REPRESENTS AN INCREASE IN
 THE CONDITIONED FLOOR AREA WHICH IS DEFINED AS AN
 ADDITION PER FBC-R SECTION N1100.7.3. ADDITIONS TO
 EXISTING RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW
 BUILDING CONSTRUCTION AND SHALL COMPLY WITH THE
 REQUIREMENTS OF EITHER METHOD A OR B AS APPLICABLE IN
 ACCORDANCE WITH FBC-R SECTION N1100.0.3. PROVIDE EITHER
 FORM 1100A-08 OR 1100B-08 COMPLIANCE FORM TO
 DEMONSTRATE ENERGY CODE COMPLIANCE.
  
 3. SHOW MEANS AND LOCATION OF DRYER EXHAUST IN
 ACCORDANCE WITH FBC-R SECTION M1502.
 NOTE: CHECK DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR MAKEUP AIR REQUIREMENTS, WHICH WILL
 NEED TO BE IN PLACE AT TIME OF FINAL INSPECTION.
  