| Plan Review Notes For Permit 09050383 |
| Permit Number |
09050383 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-04 09:15:53 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. UPDATE CODE REFERENCE ON PAGE 9.0. THE CURRENT CODE | | | IN EFFECT AS OF MARCH 1, 2009 IS THE 2007 FLORIDA | | | BUILDING CODE W/ 2009 SUPPLEMENT. | | | | | | 2. THE PROPOSED SCOPE OF WORK REPRESENTS AN INCREASE IN | | | THE CONDITIONED FLOOR AREA WHICH IS DEFINED AS AN | | | ADDITION PER FBC-R SECTION N1100.7.3. ADDITIONS TO | | | EXISTING RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW | | | BUILDING CONSTRUCTION AND SHALL COMPLY WITH THE | | | REQUIREMENTS OF EITHER METHOD A OR B AS APPLICABLE IN | | | ACCORDANCE WITH FBC-R SECTION N1100.0.3. PROVIDE EITHER | | | FORM 1100A-08 OR 1100B-08 COMPLIANCE FORM TO | | | DEMONSTRATE ENERGY CODE COMPLIANCE. | | | | | | 3. SHOW MEANS AND LOCATION OF DRYER EXHAUST IN | | | ACCORDANCE WITH FBC-R SECTION M1502. | | | NOTE: CHECK DRYER MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR MAKEUP AIR REQUIREMENTS, WHICH WILL | | | NEED TO BE IN PLACE AT TIME OF FINAL INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|